Datasheet

15 990-1060C 07/2014
Remove Battery
1. Remove front bezel and the battery door if
they are attached. (See the instructions in
the Installation section of this manual to
remove the battery door and front bezel.)
2. If the battery is connected, disconnect the
battery by pulling on the connector firmly.
3. Grasp the battery pack and slide it out of the
unit. It will stop when it is almost
completely out of the UPS. Gently move
the battery pack up and down to clear the
stop tab and slide it completely out. The
cables are attached to the battery
compartment. DO NOT pull on the cables
or the white cord while removing the
battery.
Install Battery
1. Supporting the battery pack on the bottom,
align it with the opening and slide the
battery pack into the compartment.
2. Reconnect the battery to operate the UPS.
Reattach the battery door and front bezel.
(See instructions in the Installation section
of this manual to attach the battery door and
front bezel)
Return old battery packs to APC by Schneider Electric for recycling.