Service manual

990-1008, Revision 1, 4/9945
8.3 Test of Options
Checked (
ä)
8.2.1 Check Multicom; communication is tested by means of DP-Monitor (data
transmitted).
q
8.2.2 Check Compower 5/12V.
5V Compower = 5V±0.3V
12V Compower = 10V ±1.2V
q
q
8.2.3 Check remote display driver, mount remote display, and check the indicators.
q
8.2.4 Check transformer module, fan + thermal switch OK.
q
8.2.5* Concerned calibration steps:
Step 18 ALON Alarm ON
Step 32 BYON Bypass ON
Step 33 NOBI No Burn-in
Step 35 TCMP Temperature compensation of charging
voltage
Step 37 5 Under voltage timer (seconds)
Step 40 HDIP Hardware switches active
Step 30
BATF Enter 1
Reset battery monitor
Step 20 Enter the output voltage stated in settings.
NOTE! If the output voltage has been changed during test, all AC levels are set at
default. In that case it is necessary to check that the settings correspond with the
settings stated in the test report.
Step 48 Switch the system into the operational mode stated in settings.
Enter the correct settings for the system.