Service manual
990-1008, Revision 1, 4/99 18
6.5 Smart-UPS DP is running in normal operation and mounted with Service Bypass Panel.
Service Bypass Panel is not operating.
UPS IS NOT ABLE
TO OPERATE
SERVICE BYPASS
PANEL
CHECK
FUSES ON
MEAS. &
SUPPLY
CHECK WIRING FROM
UPS TO SERVICE
BYPASS PANEL AND
FUSES INSIDE
SERVICE BYPASS
PANEL
START
END
YES
DOES UPS SWITCH
TO BYPASS OPERATION
WHEN S002 ON
SERVICE BYPASS
PANEL IS PUSHED
IS MAINS WITHIN LIMITS
FOR BYPASS
OPERATION
IS IT
POSSIBLE TO
SWITCH Q002 TO
BYPASS
YES
NO
NO
NO
YES