Operation Manual

Smart-UPS On-Line SRT5K/6K Tower/Rack-Mount 3U/4U6
Battery
*Contact APC by Schneider Electric Worldwide Customer Support to determine the age of the installed battery
modules.
CAUTION
RISK OF HYDROGEN SULPHIDE GAS AND EXCESSIVE SMOKE
Replace the battery at least every 5 years.
Replace the battery immediately when the UPS indicates battery replacement is necessary.
Replace battery at the end of its service life.
Replace batteries with the same number and type of batteries as originally installed in the equipment.
Replace the battery immediately when the UPS indicates a battery overtemperature condition, or when
there is evidence of electrolyte leakage. Power off the UPS, unplug it from the AC input, and disconnect the
batteries. Do not operate the UPS until the batteries have been replaced.
*Replace all battery modules (including the modules in External Battery Packs) which are older than one
year, when installing additional battery packs or replacing the battery module(s).
Failure to follow these instructions could result in equipment damage and minor or moderate injury.
Battery type
Sealed, maintenance-free, Valve Regulated
Lead-Acid battery
Replacement battery module
This UPS has swappable battery modules.
Refer to the appropriate replacement battery user manual for
installation instructions.
Contact your dealer or go the APC by Schneider Electric Web site,
www.apc.com for information on replacement batteries.
APCRBC140
Number of battery modules 2 battery modules
Voltage for each battery module
Total voltage for the UPS
Ah rating
96 VDC
192 VDC
5 Ah per battery module
XLBP cable length 500 mm (19.7 in)
Battery module UPS XLBP
APCRBC140 SRT5KXLx/SRT5KRMXLx/SRT6KXLx/SRT6KRMXLx SRT192BP/SRT192RMBP