Smart-UPS On-Line SRT5K/6K Tower/Rack-Mount 3U/4U24
Config
Menu
Outlets
Power On
Delay
0 seconds 0-1800 seconds Select the amount of time the controllable outlet
groups will wait between receiving the
command to turn on and actual startup.
Power Off
Delay
90 seconds 0-32767 seconds Select the amount of time the controllable outlet
groups will wait between receiving the
command to shutdown and actual shutdown.
Reboot
Duration
8 seconds 4-300 seconds Select the amount of time the controllable outlet
groups will remain off before the UPS will
restart.
Minimum
Return
Runtime
0 seconds 0-32767 seconds Select the amount of battery runtime that must
be available before the controllable outlet
groups will turn on using battery power, after a
shutdown.
Loadshed On
Battery
Disable Disable
Enable
To conserve battery power the UPS can
disconnect power from controllable outlet
groups not in use.
To configure the disconnect delay time for this
feature use the Loadshed Time On Battery
setting.
Loadshed
Time On
Battery
5 seconds 5-32767 seconds Select the amount of time the controllable outlet
groups will be allowed to function on battery
power before shutdown.
Loadshed On
Runtime
Disable Disable
Enable
To conserve battery power the UPS can
disconnect power from controllable outlet
groups when the Loadshed Runtime threshold
is reached.
Loadshed
Runtime
0 seconds 0-3600 seconds When the selected runtime threshold is reached
the UPS will shutdown the controllable outlet
groups.
Loadshed
Overload
Disable Disable
Enable
To conserve energy in the event of an overload
condition greater than 105% output, the
controllable outlet groups will immediately turn
off. The controllable outlet groups will only turn
on again with a manual restart command once
the overload condition has been corrected.
Config
Menu
Network
Manage
IP Address
Mode
Manual, DHCP,
BOOTP
Refer to the Network Management Utility CD.
IP Address
Program IP, Subnet,
Gateway
Config
Menu
Commun
ication
Modbus
Modbus Disable
Disable
Enable
Allows the user to enable or disable the UPS
Modbus functionality
Modbus
Address
1 1 - 223 Allows the user to select the Modbus address
Parameters Default Value Options Description