Operation Manual

15Smart-UPS On-Line SRT5K/6K Tower/Rack-Mount 3U/4U
SRT5KXLI/SRT6KXLI models
Input connections Single phase: Wire to L, N,
Output connections Wire to L, N
System Wiring Voltage Current full
load, nominal
External input
circuit breaker,
(typical)
Wire size,
typical
SRT5KXLI
SRT5KRMXLI
Input
Output
220/230/240 Vac 24 A 40 A/2-pole 6 mm
2
SRT6KXLI
SRT6KRMXLI
Input
220/230/240 Vac
30 A
50 A/2-pole 10 mm
2
Output 28 A
SRT5KRMXLW-HW
Input connections Single phase: Wire to L, L2/N,
Output connections Wire to L1, L2/N
System Wiring Voltage Current full
load, nominal
External input
circuit breaker,
(typical)
Wire size,
typical
SRT5KRMXLW-HW
Input
Output
208/220/
230/240 Vac
26 A
24 A
40 A/2-pole
6 mm
2
(8 AWG)