Installation Guide

Smart-UPS On-Line SRT5K/6K Tower/Rack-Mount 3U/4U 7
Electrical
CAUTION: To reduce the risk of fire, connect the UPS only to a circuit provided with recommended maximum branch
circuit overcurrent protection in accordance with the National Electrical Code, ANSI/NFPA 70 and the Canadian
Electrical Code, Part I, C22.1.
Models Rating Branch Circuit Overcurrent Rating
/ Building Circuit Breaker (CB)
Current Rating
Online Green Mode
SRT5KXLT
5.4 kVA/4.8 kW at
208 V
6.0 kVA/4.8 kW at
240 V
4.8 kVA at 208 V
5.5 kVA at 240 V
30 A
SRT5KRMXLT
SRT5KXLT-IE C
SRT5KRMXLT- IEC
SRT5KXLI
5 kVA/4.5 kW 5.0 kVA 40 ASRT5KRMXLI
SRT5KRMXLW-HW
SRT6KXLT
6 kVA/6 kW 6.0 kVA 50 A
SRT6KRMXLT
SRT6KXLT-IE C
SRT6KRMXLT- IEC
SRT6KXLI
SRT6KRMXLI
Output
Output Frequency 50 Hz/60 Hz ± 3 Hz
Nominal Output Voltage SRT5KRMXLW-HW: 208 V, 220 V, 230 V, 240 V
SRT5K/6KXLI, SRT5K/6KRMXLI: 220 V, 230 V, 240 V
SRT5K/6KXLT/XLT-IEC, SRT5K/6KRMXLT/XLT-IEC: 208 V, 240 V
Input
Input Frequency 40 HZ/70 Hz ± 3 Hz
Nominal Input Voltage SRT5KRMXLW-HW: 208 V, 220 V, 230 V, 240 V
SRT5K/6KXLI, SRT5K/6KRMXLI: 220 V, 230 V, 240 V
SRT5K/6KXLT/XLT-IEC, SRT5K/6KRMXLT/XLT-IEC: 208 V, 240 V