Installation Guide Smart-UPS™On-Line SRT5K/6K Tower/Rack-Mount 3U/4U Safety Messages SAVE THESE INSTRUCTIONS - This manual contains important instructions that should be followed during installation and maintenance of the Smart-UPS and batteries. Read these instructions carefully and look at the equipment to become familiar with the device before trying to install, operate, service or maintain it.
Safety and General Information • Adhere to all national and local electrical codes. • All wiring must be performed by a qualified electrician. • Changes and modifications to this unit not expressly approved by APC could void the warranty. • This UPS is intended for indoor use only. • Do not operate this UPS in direct sunlight, in contact with fluids, or where there is excessive dust or humidity. • Be sure the air vents on the UPS are not blocked. Allow adequate space for proper ventilation.
Battery safety • Replace batteries with the same number and type of batteries as originally installed in the equipment. • Batteries typically last for two to five years. Environmental factors impact battery life. Elevated ambient temperatures, poor quality utility power, and frequent short duration discharges will shorten battery life. Batteries should be replaced before end of life. • Replace batteries immediately when the unit indicates battery replacement is necessary.
Package Contents Inspect the contents upon receipt. Notify the carrier and dealer if the unit is damaged. Included with all models Front bezel Console to DB9 cable EPO Terminal block User Documentation CD.
Specifications For additional specifications refer to the APC by Schneider Electric Web site, www.apc.com. Environmental Temperature Maximum Elevation Operating 0º to 40º C (32º to 104º F) Storage -15º to 45º C (5º to 113º F) Operating 0 - 3,000 m (0 - 10,000 ft) Storage 0 - 15,000 m (50,000 ft) Humidity 0% to 95% relative humidity, non-condensing Protection Class IP 20 rating Note: Charge the battery modules every six months during storage. Environmental factors impact battery life.
Battery CAUTION RISK OF HYDROGEN SULPHIDE GAS AND EXCESSIVE SMOKE • Replace the battery at least every 5 years. • Replace the battery immediately when the UPS indicates battery replacement is necessary. • Replace battery at the end of its service life. • Replace batteries with the same number and type of batteries as originally installed in the equipment. • Replace the battery immediately when the UPS indicates a battery overtemperature condition, or when there is evidence of electrolyte leakage.
Electrical CAUTION: To reduce the risk of fire, connect the UPS only to a circuit provided with recommended maximum branch circuit overcurrent protection in accordance with the National Electrical Code, ANSI/NFPA 70 and the Canadian Electrical Code, Part I, C22.1. Models Rating Online SRT5KXLT SRT5KRMXLT SRT5KXLT-IEC SRT5KRMXLT-IEC 5.4 kVA/4.8 kW at 208 V Green Mode 4.8 kVA at 208 V Branch Circuit Overcurrent Rating / Building Circuit Breaker (CB) Current Rating 30 A 6.0 kVA/4.8 kW at 240 V 5.
Remove Battery Modules CAUTION RISK OF FALLING EQUIPMENT • The equipment is heavy. Each battery module weighs 17 kg (37 lb). • Always practice safe lifting techniques adequate for the weight of the equipment. • Remove the battery modules before installing the UPS. • Use the battery module handle to slide the battery modules in or out of the UPS. • Do not use the battery module handle to lift or carry the battery module.
Rack-Mount Installation Refer to the Rail Kit Installation Guide for instructions on rail installation. CAUTION RISK OF FALLING EQUIPMENT • The equipment is heavy. Always practice safe lifting techniques adequate for the weight of the equipment. • Always use the recommended number of screws to secure brackets to the UPS. • Always use the recommended number of screws and cage nuts to secure the UPS to the rack. • Always install the UPS at the bottom of the rack.
5d su0 85 a su0955 After the UPS is hardwired to branch circuit mains complete steps 8-10.
su 08 58 a a su 0859 Tower Installation CAUTION RISK OF FALLING EQUIPMENT • The equipment is heavy. Each battery module weighs 17 kg (37 lb). • Always practice safe lifting techniques adequate for the weight of the equipment. • Remove the battery modules before installing the UPS. • Use the battery module handle to slide the battery modules in or out of the UPS. • Do not use the battery module handle to lift or carry the battery module.
s u08 48c su08 48 After the UPS is hardwired to branch circuit mains complete steps 7-9. a su 08 Rotate the display panel clockwise, one quarter turn.
Rear Panel Features Note: Refer to the table “Key to identify rear panel features” on page 16, that provides a key to the callout numbers for the rear panel graphics depicted in this manual.
SRT5KXLT-IEC/SRT5KRMXLT-IEC GROUP 1 15 AMP MAX su0880a GROUP 2 20 AMP MAX Output: 50/60 Hz 208/240 VAC su0881a SRT5KRMXLW-HW SRT6KXLI/SRT6KRMXLI Output: 50/60 Hz 220/230/240 VAC su0882a GROUP 3 16 AMP MAX 14 GROUP 2 16 AMP MAX GROUP 1 10 AMP MAX Smart-UPS On-Line SRT5K/6K Tower/Rack-Mount 3U/4U
SRT6KXLT/SRT6KRMXLT GROUP 1 20 AMP MAX su0883a GROUP 2 30 AMP MAX GROUP 3 30 AMP MAX Output: 50/60 Hz 208/240 VAC SRT6KXLT-IEC/SRT6KRMXLT-IEC Output: 50/60 Hz 208/240 VAC GROUP 3 20 AMP MAX su0884a GROUP 2 20 AMP MAX GROUP 1 15 AMP MAX Smart-UPS On-Line SRT5K/6K Tower/Rack-Mount 3U/4U 15
Key to identify rear panel features SmartSlot The SmartSlot can be used to connect optional management accessories. External battery power and communication connector Use the external battery cable on the XLBP to connect the UPS and XLBP. XLBPs provide extended runtime during power outages. The UPS will automatically recognize up to 10 external battery packs. Chassis ground screws The UPS and XLBPs have ground screws for connecting the ground leads.
Wiring Specifications CAUTION RISK OF ELECTRIC SHOCK • Adhere to all national and local electrical codes. • Wiring should be performed by a qualified electrician. • Use Snap-In strain relief(s) provided with the unit. • The UPS must be wired into a branch circuit, equipped with a circuit breaker rated as specified in the tables below. • Actual wire size must comply with required amp capacity and national and local electrical codes. • Recommended input terminal screw torque: 16 lbf-in (2 Nm).
SRT5KRMXLW-HW Input connections Single phase: Wire to L, L2/N, Output connections Wire to L1, L2/N System SRT5KRMXLW-HW Wiring Voltage Current full load, nominal Input 208/220/ 230/240 Vac 26 A Output 24 A External input circuit breaker, (typical) 40 A/2-pole Wire size, typical 6 mm2 (8 AWG) Hardwire the UPS CAUTION RISK OF ELECTRIC SHOCK • Disconnect the mains input circuit breaker before installing or servicing the UPS or connected equipment.
UPS s u0 862a Output hardwiring SRT5KRMXLW-HW models su086 63 a su 08 4a L1 L2/N x2 s u08 65a x2 Smart-UPS On-Line SRT5K/6K Tower/Rack-Mount 3U/4U 19
SRT6K models Remove the 38.1 mm (1.5 in) knockout panels. a su08 66 su 08 67a su 08 68 a UPS Configuration Connect Emergency Power Off feature For instructions on how to connect the Emergency Power Off (EPO) switch, refer to the Operation and Maintenance manual on the User Documentation CD (supplied). Configure controllable outlet groups The outlets on the UPS are grouped.
UPS Display Interface POWER ON/OFF button Button illumination indications: -No illumination, the UPS and the output power are off -White illumination, the UPS and the output power are on LOAD -Red illumination, the UPS is on and the output power is off Load icon Disable/mute audible alarm icon Output 230.
Operation Mode Icons On-Line mode: The UPS is supplying conditioned mains power to connected equipment. Bypass mode: The UPS is in Bypass mode and the connected equipment will receive mains power as long as the input voltage and frequency are within the configured limits. Green mode: When in Green mode mains power is sent directly to the load. In the event of a mains power outage, there will be an interruption in power to the load of up to 10 ms while the UPS switches to On-Line mode.
Menu overview The display interface has Standard and Advanced menu screens. The preference for Standard or Advanced menu selections is made during initial installation and can be changed at any time through the Configuration menu. The Standard menus include the most commonly used options. The Advanced menus provide additional options. Note: Actual menu screens may differ by model and firmware version. Refer to the UPS Operation Manual for menu configuration details.
LCD display interface angle adjustment The angle of the LCD display interface can be adjusted for ease in viewing the displayed messages. 1. Remove the front bezel. 2. Locate the button on the bottom of the display interface panel. 3. Press the button and slide the bottom of the LCD display interface screen out. An audible click will be heard when the screen reaches the maximum angle. su 09 26 a Select models are ENERGY STAR® qualified. For more information go to www.apc.