Operation Manual Smart-UPS™ On-Line SRT SRT5KXLI SRT5KRMXLI SRT5KXLT SRT5KRMXLT SRT5KXLT-IEC SRT5KRMXLT-IEC SRT5RMKXLW-HW SRT6KXLI SRT6KRMXLI SRT6KXLT SRT6KRMXLT SRT6KXLT-IEC SRT6KRMXLT-IEC 208/220/230/240 Vac Tower/Rack-Mount 3U/4U
Product Description The APC™ by Schneider Electric Smart-UPS™ On-Line SRT is a high performance uninterruptible power supply (UPS). The UPS helps to provide protection for electronic equipment from utility power blackouts, brownouts, sags, surges, small utility power fluctuations and large disturbances. The UPS also provides battery backup power for connected equipment until utility power returns to safe levels or the batteries are completely discharged.
Safety Information • Adhere to all national and local electrical codes. • All wiring must be performed by a qualified electrician. • Changes and modifications to this unit not expressly approved by APC could void the warranty. • This UPS is intended for indoor use only. • Do not operate this UPS in direct sunlight, in contact with fluids, or where there is excessive dust or humidity. • Be sure the air vents on the UPS are not blocked. Allow adequate space for proper ventilation.
Battery safety • Before installing or replacing the batteries, remove jewelry such as wristwatches and rings. High short circuit current through conductive materials could cause severe burns. • Do not dispose of batteries by burning them. The batteries may explode. • Do not open or mutilate batteries. Released electrolyte is harmful to the skin and eyes, and may be toxic.
Product Overview Specifications For additional specifications refer to the APC web site, www.apc.com. Environmental Temperature Maximum Elevation Operating 0º to 40º C (32º to 104º F) Storage -15º to 45º C (5º to 113º F) Operating 0 - 3,000 m (0 - 10,000 ft) Storage 0 - 15,000 m (50,000 ft) Humidity 0% to 95% relative humidity, non-condensing Protection Class IP 20 rating Note: Charge the battery modules every six months during storage. Environmental factors impact battery life.
Battery Battery type Replacement battery module Maintenance free, leak proof, sealed, lead acid APCRBC140 This UPS has hot swappable battery modules. Replacement is a safe procedure, isolated from electrical hazards. Refer to the appropriate replacement battery user manual for installation instructions. Contact your dealer or go the APC web site, www.apc.com for information on replacement batteries.
Front panel features Display interface panel UPS battery connectors Battery compartment su0877a Bezel 6 Smart-UPS On-Line SRT5K/6K Tower/Rack-Mount 3U/4U
Rear panel features Note: Refer to the table “Key to identify rear panel features” on page 10, that provides a key to the callout numbers for the rear panel graphics depicted in this manual.
SRT5KXLT-IEC/SRT5KRMXLT-IEC GROUP 1 15 AMP MAX su0880a GROUP 2 20 AMP MAX Output: 50/60 Hz 208/240 VAC su0881a SRT5KRMXLW-HW 8 Smart-UPS On-Line SRT5K/6K Tower/Rack-Mount 3U/4U
SRT6KXLI/SRT6KXRMXLI Output: 50/60 Hz 220/230/240 VAC GROUP 2 16 AMP MAX su0882a GROUP 3 16 AMP MAX GROUP 1 10 AMP MAX SRT6KXLT/SRT6KRMXLT GROUP 1 20 AMP MAX su0883a GROUP 2 30 AMP MAX GROUP 3 30 AMP MAX Output: 50/60 Hz 208/240 VAC SRT6KXLT-IEC/SRT6kRMXLT-IEC Output: 50/60 Hz 208/240 VAC GROUP 3 20 AMP MAX su0884a GROUP 2 20 AMP MAX GROUP 1 15 AMP MAX Smart-UPS On-Line SRT5K/6K Tower/Rack-Mount 3U/4U 9
Key to identify rear panel features SmartSlot The SmartSlot can be used to connect optional management accessories. External battery power and communication connector Use the external battery cable on the XLBP to connect the UPS and XLBP. XLBPs provide extended runtime during power outages. The UPS will automatically recognize up to 10 external battery packs. Chassis ground screws The UPS and XLBPs have ground screws for connecting the ground leads.
Wiring Specifications CAUTION DAMAGE TO EQUIPMENT OR PERSONNEL • Adhere to all national and local electrical codes. • Wiring should be performed by a qualified electrician. • Strain reliefs are not provided with this unit. Snap-In strain reliefs are recommended. Refer to the Installation Guide for knockout panel sizes. • The UPS must be wired into a branch circuit, equipped with a circuit breaker rated as specified in the tables below.
SRT5KRMXLW-HW Input connections Single phase: Wire to L, L2/N, Output connections Wire to L1, L2/N System SRT5KRMXLW-HW Wiring Voltage Current full load, nominal Input 208/220/ 230/240 Vac 26 A Output 12 External input circuit breaker, (typical) 40 A/2-pole 24 A Smart-UPS On-Line SRT5K/6K Tower/Rack-Mount 3U/4U Wire size, typical 10 mm2 (8 AWG)
Connect Equipment CAUTION DAMAGE TO EQUIPMENT OR PERSONNEL • Disconnect the mains input circuit breaker before installing or servicing the UPS or connected equipment. • Disconnect internal and external batteries before installing or servicing the UPS or connected equipment. • The UPS contains internal and external batteries that may present a shock hazard even when disconnected from the mains. • UPS AC hardwired and pluggable outlets may be energized by remote or automatic control at any time.
UPS Display Interface POWER ON/OFF button Button illumination indications: -No illumination, the UPS and the output power are off -White illumination, the UPS and the output power are on -Red illumination, the UPS is on and the output power is off Load icon Disable/mute audible alarm icon LOA D Output 230.0 v On-Line 1 2 UPS status information Operation mode icons ESCAPE button OK button su0870b UP/DOWN buttons Controllable outlet group status icons Battery status icons .
Operation Mode Icons On-Line mode: The UPS is supplying conditioned mains power to connected equipment. Bypass mode: The UPS is in Bypass mode and the connected equipment will receive mains power as long as the input voltage and frequency are within the configured limits. Green mode: When in Green mode mains power is sent directly to the load. In the event of a mains power outage, there will be an interruption in power to the load of up to 8 ms while the UPS switches to On-Line or Battery mode.
LCD display interface angle adjustment The angle of the LCD display interface can be adjusted for ease in viewing the displayed messages. 1. Remove the front bezel. 2. Locate the button on the bottom of the display interface panel. 3. Press the button and slide the bottom of the LCD display interface screen out. An audible click will be heard when the screen reaches the maximum angle.
Configuration Menus Overview Main Menu Status Control Configuration Test And Diagnostics Log About Status Menu UPS Battery Accessory*** Control Menu** UPS Bypass Outlet Group 1* Outlet Group 2* Outlet Group 3* Clear Alarms UPS** Efficiency Output Power, VA, Watts, % Output Voltage, Current, Frequency Energy Usage Battery State Of Charge, Runtime Input Voltage, Frequency Bypass Voltage, Frequency Self Test Runtime Test Config Menu UPS Battery Outlets* Communication Display UPS** Turn On / Off / Reboot
Configuration UPS Settings There are four ways to select UPS configuration options. 1. The first time the UPS is turned on the Setup Wizard screen will open. On each menu screen select the desired settings. Press OK after each UPS setting is selected. Note: The UPS will not turn on until all of the settings have been configured. 2. Main Menu/Configuration/UPS/Load Default. This screen allows the user to reset the UPS to factory default settings. Press OK after the UPS setting is selected.
General settings Configure these settings at any time, using the display interface, or the Network Management Web Interface. Parameters Config Menu UPS Green Mode Default Value Disabled Disable Description Disable or enable Green mode operation Enable User Choice AC Setting 230 V, 220 V, 240 V, 208 V Set the output voltage for the UPS. This setting can only be changed when the UPS output is off. These settings may vary depending on the UPS model.
Parameters Config Install Date Menu Battery Default Value Options Description Battery Installation Date Month-Year Enter the installation date of the RBCs. 180 days 0-360 days To set the Near End of Life alarm, select the number of days before the estimated battery end of life. When this date is reached the UPS will emit an alarm and a message will appear on the display interface screen.
Parameters Default Value Description 0 seconds 0-1800 seconds Select the amount of time the controllable outlet groups will wait between receiving the command to turn on and actual startup. Power Off Delay 90 seconds 0-32767 seconds Select the amount of time the controllable outlet groups will wait between receiving the command to shutdown and actual shutdown.
Controllable Outlet Groups Controllable Outlet Groups provide battery backup power to connected equipment. Overview The controllable outlet groups can be configured using the Advanced menu options. Refer to “General settings” on page 18. The controllable outlet groups can be configured to independently turn off, turn on, shutdown, switch to Sleep mode, and reboot connected equipment.
Emergency Power Off Overview The Emergency Power Off (EPO) option is a feature that will immediately disconnect all connected equipment from mains power. The UPS will immediately shut down and will not switch to battery power. Connect each UPS to the EPO switch. In configurations where multiple units are connected in parallel, each UPS must be connected to the EPO switch. The UPS must be restarted for power to return to connected equipment. Press the ON/OFF button on the front panel of the UPS.
Network Management Interface Introduction The UPS has a network port and console port that can be used to access the Network Management Interface. The Network Management Interface is very similar to an AP9630 Network Management Card (NMC) that is integrated into a UPS with one universal input/output port. The Network Management Interface and the AP9630 NMC have the same firmware, operation modes and interaction with other APC products such as PowerChute Network Shutdown.
Related Documents The Network Management Card Utility CD contains the following documentation: • UPS Network Management Card 2 User’s Guide • Network Management Card Upgrade Utilities • Security Handbook • PowerNet Management Information Base (MIB) Reference Guide IP Address Configuration The default TCP/IP configuration setting DHCP, assumes that a properly configured DHCP server is available to provide TCP/IP settings to the Network Management Interface.
Smart Battery Management Definitions • Battery Module: A string of battery cells arranged to produce a battery assembly with a connector. • Replaceable Battery Cartridge (RBC): An APC battery cartridge consisting of two battery modules. Replacement RBCs can be ordered from the APC web site, www.apc.com. • Smart External Battery Pack (XLBP): An enclosure that contains RBC(s) and battery management electronics. • User Interface (UI): Any interface by which a user can interact with the system.
Replace the RBCs in a UPS An RBC should only be disconnected or removed from the UPS temporarily as part of the battery replacement procedure. • Disconnect all connected battery modules in the UPS. Slide the RBCs out of the UPS. • Slide the new RBCs into the UPS and connect the battery modules to the UPS. • Securely connect each battery module. Press the battery connector into the UPS until it is firmly connected.
Troubleshooting Use the table below to solve minor installation and operation problems. Refer to the APC web site, www.apc.com for assistance with complex UPS problems. The UPS features firmware that can be upgraded. Go to the APC web site, www.apc.com/Support, or contact your local Customer Care Center for more information. Problem and Possible Cause Solution UPS will not turn on or there is no output The UPS is not connected to mains power.
Problem and Possible Cause Solution UPS operates on battery power while connected to mains power The input circuit breaker has tripped. Reduce the load on the UPS. Disconnect nonessential equipment and reset the circuit breaker. Check the circuit breaker rating for the connected equipment. There is very high, very low, or distorted Navigate to the UPS Display Interface screen that shows input voltage. Verify that input line voltage. the input voltage is within specified operating limits.
Problem and Possible Cause Solution The UPS display turns red or amber, displays an alert message, and emits a sustained audible alarm Red illumination indicates a UPS alarm that requires immediate attention Amber illumination indicates a UPS alarm that requires attention There is an internal UPS alert or warning. Do not attempt to use the UPS. Turn the UPS off and have it serviced immediately.
Transport 1. Shut down and disconnect all connected equipment. 2. Disconnect the unit from mains power. 3. Disconnect all internal and external batteries (if applicable). 4. Follow the shipping instructions outlined in the Service section of this manual. Service If the unit requires service, do not return it to the dealer. Follow these steps: 1. Review the Troubleshooting section of the manual to eliminate common problems. 2.
Limited Factory Warranty Schneider Electric IT Corporation (SEIT), warrants its products to be free from defects in materials and workmanship for a period of three (3) years excluding the batteries, which are warranted for two (2) years from the date of purchase. The SEIT obligation under this warranty is limited to repairing or replacing, at its own sole option, any such defective products. Repair or replacement of a defective product or part thereof does not extend the original warranty period.
APC by Schneider Electric Worldwide Customer Support Customer support for this or any other APC by Schneider Electric product is available at no charge in any of the following ways: • Visit the APC web site to access documents in the APC by Schneider Electric Knowledge Base and to submit customer support requests. – www.apc.com (Corporate Headquarters) Connect to localized APC web site for specific countries, each of which provides customer support information. – www.apc.