Datasheet

Smart-UPS On-Line SRT2200/SRT3000 Tower/Rack-Mount 2U16
Config
Menu
UPS
Site Wiring
Fault
(For XLI and
XLW models
only)
Disable Disable
•User Can
Acknowledge
Enable
Allows the user to configure the behavior of
the UPS in response to the site wiring fault
alert which is generated due to wrong input AC
mains connection with input phase and neutral
reversed.
Disable: The UPS never indicates site wiring
fault to the user.
User Can Acknowledge: UPS alerts the user
about site wiring fault, when detected. The
alert is active till the user acknowledges it by
pressing OK.
Enable: UPS alerts the user about site wiring
fault, when detected. The alert cannot be reset
until the site wiring fault is corrected.
PDU Model Standard SRT011 and SRT012
for XLT and XLW
models
SRT012 for XLI
models
Select the PDU model installed in the UPS for
proper operation of the PDU.
See the user documentation for the PDU
models SRT011and SRT012 for details.
Default
Setting
No Yes/No Allows the user to restore the UPS factory default
settings.
Reset Energy
Meter
No Yes/No The Energy Meter stores information on UPS output
energy usage.
The Reset feature allows the user to reset the
Energy Meter to 0 kWh.
Config
Menu
Battery
Install Date
Battery Installation
Date
Month-Year
Enter the installation date of the RBCs.
Replacement
Notification
Time
180 days 0-360 days To set the Near End of Life audible alarm, select
the number of days before the estimated battery end
of life.
When this date is reached the UPS will emit an
audible alarm and a message will appear on the
display interface screen.
Example: Using the default value, the Near End of
Life audible alarm will occur 180 days before the
estimated end of life date.
Replacement
Battery
Alarm Time
14 days 0-180 days
The Near End of Life audible alarm can be
muted. Enter the number of days between the
time a Near End of Life audible alarm is
acknowledged and the next Near End of Life
audible alarm occurs.
Parameters Default Value Options Description