Smart-UPS On-Line SRT2200XLA/SRT3000XLA Tower/Rack-Mount 2U6
Electrical
Front Panel Features
Models Max. Rating
Branch Circuit
Overcurrent Rating /
Building Circuit Breaker
(CB) Current Rating
Online Green Mode
SRT2200XLA 2200 VA / 1800 W 1800 VA 20 A
SRT2200RMXLA/SRT2200RMXLA-NC
SRT3000XLA 3000 VA / 2700 W 2700 VA 30 A
SRT3000RMXLA/SRT3000RMXLA-NC
CAUTION
RISK OF FIRE, RISK OF DAMAGE TO EQUIPMENT OR PERSONNEL
Connect the UPS models only to a circuit provided with recommended maximum branch circuit overcurrent protection in
accordance with the National Electrical Code, ANSI/NFPA 70 and the Canadian Electrical Code, Part I, C22.1.
Failure to follow these instructions can result in fire, equipment damage and minor or moderate injury.
Output
Output Frequency 50 Hz / 60 Hz (Selectable)
Nominal Output Voltage 120 V
Input
Input Frequency 40 Hz - 70 Hz
Nominal Input Voltage 120 V
Nominal Input Current SRT2200 models: 16 A
SRT3000 models: 24 A
Display interface panel
UPS battery connectors
Battery module
Bezel
suo0860a