5Smart-UPS On-Line SRT2200XLA/SRT3000XLA Tower/Rack-Mount 2U
Battery
NOTICE
RISK OF EQUIPMENT DAMAGE
• Replace the battery at least every 5 years.
• Replace the battery immediately when the UPS indicates battery replacement is necessary.
Failure to follow these instructions can result in equipment damage
SRT2200 models SRT3000 models
Battery type
Sealed, maintenance-free, Valve Regulated
Lead-Acid battery
Replacement battery module
This UPS has swappable battery modules.
Refer to the appropriate replacement battery user manual for
installation instructions.
Contact your dealer or go the APC by Schneider Electric web site,
www.apc.com for information on replacement batteries.
APCRBC141 APCRBC152
Number of battery modules 1 battery module
Voltage for each battery module 72 VDC 96 VDC
Total battery voltage for the UPS 72 VDC 96 VDC
Ah rating 5 Ah per battery module
XLBP cable length 500 mm (19.7 in)