25Smart-UPS On-Line SRT2200XLA/SRT3000XLA Tower/Rack-Mount 2U
The UPS display turns red or amber, displays an alert message, and emits a sustained audible alarm.
Red illumination indicates a UPS alarm that requires immediate attention.
Amber illumination indicates a UPS alarm that requires attention.
There is an internal UPS alert or
message.
Do not attempt to use the UPS. Turn the UPS off and have it serviced
immediately.
The UPS is experiencing an overload
condition.
Reduce the load on the UPS. Disconnect nonessential equipment.
The UPS has detected a Site Wiring
Fault.
Correct the building site wiring fault or ignore this message. See Config
Menu UPS in “General settings” on page 14.
The Replace Battery alert is displayed
The battery has a weak charge. Allow the battery to recharge for at least four hours. Then, perform a
UPS Self Test. If the problem persists after recharging, replace the battery.
The replacement battery is not properly
connected.
Be sure the battery cable is securely connected.
Problem and Possible Cause Solution
1/1
Power Sys Error - 00100
Contact Customer Support
Output Off
12
1/1
Output Overload
Bypass
12
1/1
Site Wiring Fault
Press OK to Clear Alarm
Online Green
12