User Manual

Smart-UPS On-Line SRT2200XLA/SRT3000XLA Tower/Rack-Mount 2U16
Config
Menu
Display
Language
English
English
Francais
Italiano
Deutsch
Espanol
Portugues
Russian
Select the language required for the display
interface.
Language options will vary by model and firmware
version.
Audible
Alarm
Enable
Disable
Enable
When audible alarms are disabled, the UPS will
never emit an audible alarm.
LCD
Back Light
Auto Dim Always On
Auto Dim
Auto Off
To conserve energy, the LCD back light illumination
dims or turns off when no events are active.
Full display interface illumination returns when the
UPS changes status as a result of an event or when
any button on the display interface is pressed.
LCD Setting
Optimal Values Color
Brightness
Contrast
Adjust the brightness and contrast individually for
each LCD back light color.
Menu Type
User Choice Standard
Advanced
The Standard menus include the most commonly
used options.
The Advanced menu options include all parameters.
Time
UTC time DD-MMM-YYYY
HH:MM:SS am/pm
Scroll through the fields to set the time.
Config
Menu
Outlets
Power On
Delay
0 seconds 0-1800 seconds Select the amount of time the controllable outlet
groups will wait between receiving the command to
turn on and actual startup.
Power Off
Delay
90 seconds 0-32767 seconds Select the amount of time the controllable outlet
groups will wait between receiving the command to
shutdown and actual shutdown.
Reboot
Duration
8 seconds 4-300 seconds Select the amount of time the controllable outlet
groups will remain off before the UPS will restart.
Minimum
Return
Runtime
0 seconds 0-32767 seconds Select the amount of battery runtime that must be
available before the controllable outlet groups will
turn on using battery power, after a shutdown.
Loadshed
Time On
Battery
Disable Disable
Enable
To conserve battery power the UPS can disconnect
power from controllable outlet groups not in use.
To configure the disconnect delay time for this
feature use the Loadshed Time On Battery setting.
Loadshed
Time On
Battery
5 seconds 5-32767 seconds Select the amount of time the controllable outlet
groups will be allowed to function on battery power
before shutdown.
Loadshed On
Runtime
Disable Disable
Enable
To conserve battery power the UPS can disconnect
power from controllable outlet groups when the
Loadshed Runtime threshold is reached.
Loadshed
Runtime
0 seconds 0-3600 seconds When the selected runtime threshold is reached the
UPS will shutdown the controllable outlet groups.
Loadshed On
Overload
Disable Disable
Enable
To conserve energy in the event of an overload
condition greater than 105% output, the controllable
outlet groups will immediately turn off. The
controllable outlet groups will only turn on again
with a manual restart command once the overload
condition has been corrected.
Parameters Default Value Options Description