15Smart-UPS On-Line SRT2200XLA/SRT3000XLA Tower/Rack-Mount 2U
Config
Menu
UPS
Site Wiring
Fault
User Can
Acknowledge
• Disable
• Enable
•User Can
Acknowledge
Allows the user to configure the behavior of
the UPS in response to the site wiring fault
alert which is generated due to wrong input AC
mains connection with input phase and neutral
reversed.
Disable: The UPS never indicates site wiring
fault to the user.
Enable: UPS alerts the user about site wiring
fault, when detected. The alert cannot be reset
until the site wiring fault is corrected.
User Can Acknowledge: UPS alerts the user
about site wiring fault, when detected. The
alert is active till the user acknowledges it by
pressing OK.
PDU Model Standard SRT012 Select the PDU model installed in the UPS for
proper operation of the PDU.
Default
Setting
No Yes/No Allows the user to restore the UPS factory default
settings.
Reset Energy
Meter
No Yes/No The Energy Meter stores information on UPS output
energy usage.
The Reset feature allows the user to reset the
Energy Meter to 0 kWh.
Config
Menu
Battery
Install Date
Battery Installation
Date
Month-Year Enter the installation date of the RBCs.
Replacement
Notification
Time
180 days 0-360 days To set the Near End of Life audible alarm, select
the number of days before the estimated battery end
of life.
When this date is reached the UPS will emit an
audible alarm and a message will appear on the
display interface screen.
Example: Using the default value, the Near End of
Life audible alarm will occur 180 days before the
estimated end of life date.
Replacement
Battery
Alarm Time
14 days 0-180 days The Near End of Life audible alarm can be muted.
Enter the number of days between the time a Near
End of Life audible alarm is acknowledged and the
next Near End of Life audible alarm occurs.
Parameters Default Value Options Description