User Manual

9Smart-UPS On-Line SRT2200XLA/SRT3000XLA Tower/Rack-Mount 2U
Operation
Connect Equipment
Note: The UPS batteries will charge to 90% capacity in the first three hours of normal operation. Do not expect full
battery runtime capability during this initial charge period.
1. Connect the internal battery module. See Installation manual for details.
2. Connect equipment to the outlets on the rear panel of the UPS.
Refer to “Controllable Outlet Groups” on page 18.
3. Connect the UPS to the building utility power.
Turn the UPS On/Off
The first time the UPS is turned on the Setup Wizard screen will run. Follow the prompts to configure UPS settings.
Refer to “Configuration” on page 13.
To turn on the UPS and all connected equipment, press the
POWER ON/OFF button on the display panel. Follow the
prompts to either turn the UPS on immediately or after a delay, then press OK.
NOTE: When there is no input power and the UPS is off, the cold start feature can be used to turn on the UPS and
connected equipment using battery power.
To perform a cold start press the
POWER ON/OFF button.
The display panel will illuminate and the
POWER ON/OFF button will illuminate red.
To turn on the output power press the
POWER ON/OFF button again. Select the prompt Turn ON with NO AC and press
OK.
To turn output power off, press the
POWER ON/OFF button. Follow the prompts to either turn the UPS off immediately or
after a delay, then press OK.
NOTE: Once the UPS output power has been turned off and the AC input has been removed, the UPS will continue to
use the battery for internal power for 10 minutes. To remove power completely press the
POWER ON/OFF button. Follow
the prompt to select Internal Power Off, then press OK.
CAUTION
DAMAGE TO EQUIPMENT OR PERSONNEL
• Disconnect the mains input circuit breaker before installing or servicing the UPS or connected equipment.
• Disconnect internal and external batteries before installing or servicing the UPS or connected equipment.
The UPS contains internal and external batteries that may present a shock hazard even when disconnected from the
mains.
UPS AC hardwired and pluggable outlets may be energized by remote or automatic control at any time.
• Disconnect equipment from the UPS before servicing any equipment.
Failure to follow these instructions can result in equipment damage and minor or moderate injury.