Installation Manual
Table Of Contents
- Important Safety Messages
- Safety and General Information
- Deenergizing safety
- Electrical safety
- Battery safety
- General information
- FCC Class A radio frequency warning
- Package Contents
- Inspect the contents upon receipt. Notify the carrier and dealer if the unit is damaged.
- Specifications
- Environmental
- Physical
- Battery
- Electrical
- Remove Battery Module
- Rack-Mount Installation
- Tower Installation
- Rear Panel Features
- Key to identify rear panel features
- UPS Configuration
- Connect Emergency Power Off feature
- Verify input connection
- Configure controllable outlet groups
- UPS Display Interface
- Display interface operation
- Menu overview
- LCD display interface angle adjustment
- Select models are ENERGY STARĀ® qualified. For more information go to www.apc.com/company/us/en/sustainability/energy-efficiency/
Smart-UPS On-Line SRT2200XLA/SRT3000XLA Tower/Rack-Mount 2U6
Electrical
Models Rating
Branch Circuit
Overcurrent Rating /
Building Circuit Breaker
(CB) Current Rating
Online Green Mode
SRT2200XLA 2200 VA / 1800 W 1800 VA 20 A
SRT2200RMXLA/SRT2200RMXLA-NC
SRT3000XLA 3000 VA / 2700 W 2700 VA 30 A
SRT3000RMXLA/SRT3000RMXLA-NC
CAUTION
RISK OF FIRE, RISK OF DAMAGE TO EQUIPMENT OR PERSONNEL
Connect the UPS models only to a circuit provided with recommended maximum branch circuit overcurrent protection in
accordance with the National Electrical Code, ANSI/NFPA 70 and the Canadian Electrical Code, Part I, C22.1.
Failure to follow these instructions can result in fire, equipment damage and minor or moderate injury.
Output
Output Frequency 50 Hz / 60 Hz (Selectable)
Nominal Output Voltage 120 V
Input
Input Frequency 40 Hz - 70 Hz
Nominal Input Voltage 120 V
Nominal Input Current SRT2200 models: 16 A
SRT3000 models: 24 A