Owners manual
Smart-UPS X 2000/2200/3000 Vac XL 120/208/230/240 VA Tower/Rack-Mount 4U
13
Customize Switched Outlet Groups
Use the Control menus to customize the Switched Outlet Groups.
Network Management Card settings
These settings are available only on units that have a Network Management Card (NMC).
• NMC IP Address Mode
• NMC Default Gateway
Function Factory Default Options Description
Name String
Outlet Group
Outlet Groups
1, 2, 3
Edit these names using an external interface, such as the Network
Management Card web interface.
UPS Name String APC UPS
Turn On Delay 0 sec Set the value in
seconds
The amount of time the Switched Outlet Groups will
wait between receiving the command to turn on and the
actual startup.
Turn Off Delay 90 sec Set the value in
seconds
The amount of time that the Switched Outlet Groups
will wait between receiving the command to turn off
and the actual shut down.
Reboot Duration 8 sec Set the value in
seconds
The amount of time that the Switched Outlet Groups
must remain off before it will restart.
Minimum Return
Time
0 sec Set the value in
seconds
The amount of battery runtime that must be available
before the Switched Outlet Groups will turn on again
after a shutdown.
Load Shed On
Battery
Disabled • Shutdown with
Delay
• Shutdown
immediately
• Turn off
immediately
• Turn off with
delay
• Disabled
When the unit switches to battery power, the UPS can
disconnect power to the Switched Outlet Groups to
save runtime.
Configure this delay time, use the
LOAD SHED TIME
WHEN ON BATTERY setting.
Load Shed Time
when On Battery
Disabled Set the value in
seconds
The amount of time the outlets will function on battery
power before they will turn off.
Load Shed On
Runtime
Disabled • Shutdown with
delay
• Shutdown
immediately
• Turn off
immediately
• Turn off with
delay
• Disabled
Configure this time using the
LOAD SHED RUNTIME
R
EMAINING setting.
Load Shed On
Runtime Remaining
Disabled Set the value in
seconds
When the remaining runtime reaches this level, the
Switched Outlet Groups will turn off.
Load Shed on
Overload
Disabled • Disabled
• Enabled
In the event of an overload (greater than 105% output),
the Switched Outlet Groups will immediately turn off
to conserve power for critical loads. The Switched
Outlet Groups will only turn on again with a manual
command.