Switched Outlet Groups
Note: Switched Outlet Groups provide battery backup power to connected equipment.
Overview
The Switched Outlet Groups can be configured to independently turn off, turn on, shut down, go into sleep mode,
and reboot connected equipment.
The Switched Outlet Groups can be configured to do the following:
Turn off: Disconnect from power immediately and restart only with a manual command
Turn on: Connect to power immediately
Shutdown: Disconnect power in sequence, and automatically reapply power in sequence when utility power
becomes available
Reboot: Shut down and restart
Sleep: Reboot after a long delay
In addition, the Switched Outlet Groups can be configured to do the following:
Turn on or off in a specified sequence
Automatically turn off or shut down when various conditions occur
Use of Switched Outlet Groups
1. Connect critical equipment to a Switched Outlet Group.
2. Connect peripheral equipment to the other Switched Outlet Groups.
During a power outage, to conserve battery runtime, nonessential equipment can be
configured to shut down after a short delay
If equipment has dependent peripherals that must restart or shut down in a specific order, such
as an ethernet switch that must restart before a connected server, connect the devices to
separate groups
Equipment that needs to reboot independently from other equipment should be connected to a
separate group
3. Use the Configuration menus to configure how the Switched Outlet Groups will react in the
event of a power outage.