Installation Guide
Table Of Contents
Smart-UPS 750/1000/1500/2200/3000 VA 120/208/230 Vac Rack-Mount 2U 3
Installation
*Contact APC by Schneider Electric Worldwide Customer Support to determine the age of the installed battery modules.
120/208/230 Vac models
(1) (1) (1)
230 Vac models
(2)
(1) 2200/3000 VA models
(1) 2200/3000 VA models
(1) 2200/3000 VA models
CAUTION
RISK OF DROPPED OR FALLING EQUIPMENT
• The equipment is heavy. Always practice safe lifting techniques adequate for the weight of the
equipment.
• Remove the battery before installing the UPS in a rack.
• When installing equipment in a rack, always install the UPS at the bottom of the rack with the peripheral
equipment above the UPS.
• The UPS should always be installed below peripheral equipment in stack or rack configurations.
Failure to follow these instructions can result in equipment damage and minor or moderate injury.
CAUTION
RISK OF HYDROGEN SULPHIDE GAS AND EXCESSIVE SMOKE
• Replace the battery at least every 5 years.
• Replace the battery immediately when the UPS indicates battery replacement is necessary.
• Replace battery at the end of its service life.
• Replace batteries with the same number and type of batteries as originally installed in the equipment.
• Replace the battery immediately when the UPS indicates a battery overtemperature condition, or when
there is evidence of electrolyte leakage. Power off the UPS, unplug it from the AC input, and
disconnect the batteries. Do not operate the UPS until the batteries have been replaced.
• *Replace all battery modules (including the modules in External Battery Packs) which are older than
one year, when installing additional battery packs or replacing the battery module(s).
Failure to follow these instructions could result in equipment damage and minor or moderate
injury.