User's Manual

Smart-UPS 750/1000/1500/2200/3000 VA 120/230 Vac Tower / Rack-Mount 2U 19
Outlet group configuration settings
The Main Outlet Group and the Controlled Outlet Group can be configured to independently turn off, turn on, shut
down, and reboot connected equipment.
The Main and Controlled Outlet Groups can be configured to do the following:
Turn off: Disconnect from power immediately and restart only with a manual command.
Turn on: Connect to power immediately.
Shutdown: Disconnect power in sequence, and automatically reapply power in sequence when AC power
becomes available.
Reboot: Shut down and restart.
In addition, the Main Outlet Group and the Controlled Outlet Group can be configured to do the following:
Turn on or off in a specified sequence
Automatically turn off or shut down when various conditions occur
Note: If the Main and Controlled Outlet Groups are not configured, all of the outlets on the unit will still provide
battery back-up power.
Note: The Main Outlet Group functions as a master switch. It will turn on first when power is applied, and shut off
last when there is a power outage and battery run-time has been exhausted.
The Main Outlet Group must be turned on for the Controlled Outlet Group to turn on.
Green Mode Enable Enable
•Disable
This will enable or disable Green mode
function. Green Mode conserves energy
while the UPS is operating on line.
SmartConnect
Control
Enable Enable
•Disable
This will permit remote configuration
changes.
Low Battery
Setting
150 sec Set the value in seconds The UPS will emit an audible alarm when
the remaining runtime has reached this
level.
Install FW? Don’t Install Next off (Updates the UPS
Firmware next time that the UPS is
turned off)
Now (Updates the UPS firmware
immediately without interrupting
operations)
Don't Install
Firmware update: this only appears when
new firmware is available in the flash
memory of the UPS and is ready to be
installed
Setting Factory Default Options Description
Name String
Outlet Group
Outlet Group 1 Edit these names using an external interface, such as the Network
Management Card Web interface.
UPS Name String UPS Outlets
Turn On Delay 0 sec Set the value in seconds The amount of time the UPS or the Controlled
Outlet Group will wait between receiving the
command to turn on and the actual startup.
Turn Off Delay 0 sec (UPS Outlets)
90 sec (Controlled
Outlet Groups)
Set the value in seconds The amount of time the UPS or the Controlled
Outlet Group will wait between receiving the
command to turn off and the actual shut down.
Reboot Duration 8 sec Set the value in seconds The amount of time that the UPS or the Controlled
Outlet Group must remain off before it will restart.
Minimum Return
Time
0 sec Set the value in seconds The amount of battery runtime that must be
available before the UPS or the Controlled Outlet
Group will turn on.
Setting Factory Default Options Description