13Smart-UPS 750-3000 VA 100/120/208/230 Vac Rack-Mount
Network Management Card Settings
These settings are available only on units that have a Network Management Card (NMC) and are set in the factory.
These settings can only be modified using an external interface, like the NMC web interface.
• NMC IP Address Mode
• NMC IP Address
• NMC Subnet Mask
• NMC Default Gateway
Function Factory Default Options Description
Name String
Outlet Group
Outlet Group 1
Edit these names using an external interface, such as the Network
Management Card Web interface.
UPS Name String UPS Outlets
Turn On Delay 0 sec Set the value in
seconds
The amount of time the UPS or
the Switched Outlet
Group
will wait between receiving the command to
turn on and the actual startup.
Turn Off Delay • 0 sec (UPS Outlets)
• 90 sec (Switched
Outlet Groups)
Set the value in
seconds
The amount of time that the UPS or
the Switched
Outlet Group
will wait between receiving the
command to turn off and the actual shut down.
Reboot Duration 8 sec Set the value in
seconds
The amount of time that the UPS or
the Switched
Outlet Group
must remain off before it will restart.
Minimum Return
Time
0 sec Set the value in
seconds
The amount of battery runtime that must be available
before the UPS or
the Switched Outlet Group will turn
on.
Load Shed On
Battery
Disabled • Shutdown with
Delay
• Shutdown
immediately
• Turn off
immediately
• Turn off with delay
• Disabled
When the unit switches to battery power, the UPS can
disconnect power to the
Switched Outlet Group to
save runtime.
Configure this delay time, use the
LOAD SHED TIME
WHEN ON BATTERY setting.
Load Shed Time
when On Battery
Disabled Set the value in
seconds
The amount of time the outlets will function on battery
power before they will turn off.
Load Shed On
Runtime
Disabled • Shutdown with
delay
• Shutdown
immediately
• Turn off
immediately
• Turn off with delay
• Disabled
When the battery runtime falls below the specified
value, the
Switched Outlet Group will turn off.
Configure this time using the
LOAD SHED RUNTIME
R
EMAINING setting.
Load Shed On
Runtime
Remaining
Disabled Set the value in
seconds
When the remaining runtime reaches this level, the
Switched Outlet Group will turn off.
Load Shed on
Overload
Disabled • Disabled
• Enabled
In the event of an overload (greater than 100% output),
the
Switched Outlet Group will immediately turn off
to conserve power for critical loads. The
the Switched
Outlet Group
will only turn on again with a manual
command.