Operation Manual

11Smart-UPS 750-3000 VA 100/120/208/230 Vac Rack-Mount
Low Transfer
Point
100 Vac:
92 Vac
•86 Vac
•88 Vac
•90 Vac
•92 Vac
Set the transfer point lower if the utility voltage is
chronically low and the connected equipment can tolerate
this condition.This setting may also be adjusted using the
power quality setting.
Note: Use the Advanced Menus to configure this setting.
120 Vac:
106 Vac
•97 Vac
•100 Vac
•103 Vac
•106 Vac
208 Vac:
182 Vac
•170 Vac
•174 Vac
•178 Vac
•182 Vac
230 Vac:
208 Vac
•196 Vac
•200 Vac
•204 Vac
•208 Vac
Nominal Output
Vol t age
100 Vac N/A Set the nominal output voltage of the UPS on battery. This
is available on 230 Vac models only.
120 Vac N/A
230 Vac 208-252 Vac
Transfer
Sensitivity
High High, Reduced, Low Select the level of sensitivity to power events that the UPS
will tolerate.
High: The UPS will go on battery power more often to
provide the cleanest power supply to the connected
equipment.
Low: The UPS will tolerate more fluctuations in power
and will go on battery power less often.
If the connected load is sensitive to power disturbances, set
the sensitivity to High.
Low Battery
Alert
120 sec Set the value in
seconds
The UPS will emit an audible alarm when the remaining
runtime has reached this level.
Date of Last
Battery
Replacement
Date set at factory Reset this date when the battery module is replaced.
Audible Alarm On On/Off The UPS will mute all audible alarms if this is set to Off or
when the display keys are pressed.
Battery Self-
Test Interval
Setting
On start-up and
every 14 days since
the last test
•Never
Start-up only
Frequency of test
(every 7 to 14 days)
The interval at which the UPS will execute a self-test.
Reset to Factory
Default
No Yes/No Restore the UPS factory default settings.
Function Factory Default Options Description