Smart-UPS 750-3000 VA 100/120/208/230 Vac Rack-Mount10
Configuration
UPS Settings
Start-up Settings
Configure these settings at initial start-up, using the display interface. As an alternative, configuration can be
performed using APC by Schneider Electric PowerChute
™
software.
Note: During start-up, use the display interface to configure these settings. If nothing is selected, the unit will use
the default settings.
General Settings
Configure these settings at any time, using the display interface or PowerChute software.
Function Factory Default Options Description
Language English • English
• French*
•German*
• Spanish*
•Italian*
• Portuguese*
• Japanese*
The language for the display interface.
*Language options will vary by model.
Local Power
Quality
Good • Good
•Fair
•Poor
Select the quality of input utility power.
• If Good is selected, the unit will go on battery power more often
to provide the cleanest power supply to the connected
equipment.
• If Poor is selected, the UPS will tolerate more fluctuations in
power and will go on battery power less often.
If unsure of the local power quality, select Good.
Menu Type Standard Standard or
Advanced
The Standard menus display a limited set of menus and options.
The Advanced menus include all parameters.
Function Factory Default Options Description
High Transfer
Point
100 Vac:
108 Vac
•108 Vac
• 110 Vac
• 112 Vac
• 114 Vac
To avoid unnecessary battery usage, set the transfer point
higher if the utility voltage is chronically high and the
connected equipment is known to work under this
condition. The
POWER QUALITY setting will automatically
change this setting.
Note: Use the Advanced Menus to configure this setting.
120 Vac:
127 Vac
•127 Vac
•130 Vac
•133 Vac
•136 Vac
208 Vac:
225 Vac
•225 Vac
•229 Vac
•233 Vac
•237 Vac
230 Vac:
253 Vac
•253 Vac
•257 Vac
•261 Vac
•265 Vac