Configuration
General configuration settings
Configuration settings may be changed at any time using the LCD interface or PowerChute software. This table
provides a brief description of the general settings, for more detailed information on each of these parameters
consult application note 80 at www.apc.com.
Function Factory Default Options Description
High Transfer 120 V: 127 Vac
230 V: 253 Vac
127 Vac - 136 Vac
253 Vac - 265 Vac
To avoid unnecessary battery usage, set the transfer point
higher if the AC voltage is chronically high and the
connected equipment is known to work under this
condition. The Power Quality setting will automatically
change this setting.
Note: Use the Advanced Menus to configure this setting.
Low Transfer 120 V: 106 Vac
230 V: 207 Vac
97 Vac - 106 Vac
195 Vac - 207 Vac
Set the transfer point lower if the AC voltage is chronically
low and the connected equipment can tolerate this
condition. This setting may also be adjusted using the
power quality setting.
Note: Use the Advanced Menus to configure this setting.
Sensitivity Normal Normal
Reduced
•Low
Select the level of sensitivity to power events that the UPS
will tolerate.
Normal: The UPS will go on battery power more often to
provide the cleanest power supply to the connected
equipment.
Low: The UPS will tolerate more fluctuations in power
and will go on battery power less often.
If the connected load is sensitive to power disturbances, set
the sensitivity to Normal.
Date of Last
Battery
Replacement
Date set at factory. Reset this date when the battery module is replaced.
Audible Alarm On On
•Off
The UPS will mute all audible alarms if this is set to Off or
when the display buttons are pressed.
Auto Self Test On start-up and
every 14 days
since the last test
Never
Start-up only
Frequency of test
(every 7 to 14 days)
The interval at which the UPS will execute a self-test.
Reset to Factory
Default
No Yes/No Restore the UPS factory default settings.
Site Wiring Fault Enable Enable/Disable/
Can Ack
Set the Site Wiring Fault detection to Enable, Disable or
User Can Acknowledge
Output voltage 120 V
230 V
120Vac
110Vac
127Vac
230 Vac
220 Vac
240 Vac
Select the output voltage. This is only settable when the
UPS is turned off.
Green Mode Enable Enable
•Disable
This will enable or disable Green mode function. Green
Mode conserves energy while the UPS is operating on line.
SmartConnect
Control
Enable Enable
•Disable
This will permit remote configuration changes.