User Guide

Smart-UPS C 1000/1500 VA 120/230 Vac Tower / Rack-Mount 2U 13
Output Voltage
Setting
for 120V models: 110 -> 120 -> 127
for 230V models: 220 -> 230 -> 240
Select the output voltage (not available on some models)
LCD Energy Save
Mode
dP.0 = disable
•dP.1 = enable
dP.1 - Enabled (Default) - When enabled the LCD will
automatically dim after 60 seconds of no activity
dP.0 - Disabled - The display will stay illuminated
indefinitely.
Communication
Protocol
cP.0 = disable
•cP.1 = enable
Enables / disables the Modbus communication protocol.
cP.1 (enabled) is the default.
Green Mode Enable
0: Disable
1: Enable
When Green Mode is enabled the UPS is operating at the
most efficient level by bypassing unused AVR
components while acceptable AC voltage is present. The
UPS will enter and exit Green mode automatically while
Enabled.
Enabled is the default.
SmartConnect remote
commands
rc.0: remote control disable
rc.1: remote control enable
When enabled, it allows SmartConnect to send
commands and configuration to the UPS.
rc.0, disabled, is the default.
Battery Replaced
rb.0: No battery replacement
rb.1: Battery replaced
rb.0 - Did not replace battery (default)
rb.1 - Battery has been replaced
Select rb.1 to indicate that the battery has been replaced,
this will reset the constants for the battery runtime
calibration to the default for a new battery.
Function Options Description
su0740l
su0740m
su0740n
su0740o