User Guide
Smart-UPS C 1000/1500 VA 120/230 Vac Tower / Rack-Mount 2U12
Function Options Description
Firmware Upgrade
•UP.0
UP.0 = firmware valid and different
from current running firmware
•UP.1
UP.1 = confirm the firmware update
•UPd
UPd = firmware update in progress
This mode only appears when firmware is stored in
memory, and different from the current firmware running.
UP.0 indicates new firmware is available and different
from current firmware, but will not install until instructed
by user.
Pressing MUTE instructs the UPS to install new firmware,
and changes the display to UP.1.
UP.1 indicates system is ready for firmware installation.
Press MENU to install the firmware and exit
Configuration Mode; or press MUTE to revert to UP.0
(canceling firmware installation).
Self-Test
• 0: Default Setting
• 1: Begin Self-Test
Default setting St.0, indicates that a Self Test has not been
requested
Pressing MUTE requests a Self Test and changes display
to St.1.
Press MENU to begin Self Test and exit Configuration
Mode, or MUTE to revert to St.0 (canceling Self test).
Note: Self tests operate only when the output is on.
Power Quality
• Good
•Fair
• Poor
Select the Sensitivity range depending on the desired
quality of output AC power:
• Pq.3: (Default) Good - If selected, the unit will go on
battery power more often to provide the cleanest power
supply to the connected equipment. Use this setting
when the input power is normally good as it provides
the cleanest power supply to the connected load.
• Pq.2 - Fair should be selected if the unit is operating on
battery too often on the high setting. It makes the unit
less sensitive to disturbances in input power. Use this
setting when the line input has frequent variations.
• Pq.1 - If Poor is selected, the UPS will tolerate more
fluctuations in power and will go on battery power less
often.
The unit ships from the factory at the Good setting.