User manual

User Manual Smart-UPS RC UXI/UXICH 1000/2000/3000 VA 220/230/240 Vac Tower/Rack-Mount 4U 19
Configure UPS connection settings using UPS terminal mode
Connect the serial cable to the serial port on the back of the UPS. If using USB communication to the UPS,
disconnect USB cable prior to connecting serial cable.
1. Open a terminal program, such as HyperTerminal
From the Desktop, go to: Start, Programs, Accessories, Communication, HyperTerminal
2. Follow the prompts to choose a name and select an icon. Disregard the message, "...must install a
modem," if it is displayed. Click Cancel
3. Go to File, Properties. Select the COM port that is connected to your UPS. The port settings are:
bits per second - 2400
data - bits 8
parity - none
stop bit - 1
flow control - none
4. Click OK in each of two windows
5. Press ENTER
Configure the number of battery strings using UPS terminal mode
1. Once the blank terminal window is open, follow these steps to enter the number of battery strings:
NOTE: Letter key commands are case sensitive. Use capital letters when using letter key commands.
2. Press Y. The UPS will respond with SM in the command box. If the UPS does not respond to the
Y command, ensure the serial cable is securely connected to the serial port on the UPS. Use only
an APC supplied serial cable.
3. When SM appears in the command box press the > key. The UPS will respond with the number of
battery strings connected to the UPS. If the UPS has not been previously programmed to
recognize the number of battery strings this number will be zero.
4. Use the + or - keys to change the number of battery strings. OK will appear in the command box.
5. Press > key. The number of battery strings will appear in the command box.
NOTE: The + or - keys and the > key must be used again to change the number of battery strings
from this point in the programming.
6. Press R. The UPS will respond with BYE in the command box.