SRC96XLBP / SRC96XLBP2S User Manual 13
Smart-UPS SRC XLI Models - Configure Number of Battery Strings
Each 96 V battery string consists of two 48 V battery modules. Count the number of battery strings being used and
enter that number.
Configuration # of Battery
Strings
Factory Default
for all Models
UPS internal battery string 1
SRC96XLBP2S
UPS internal battery string + 1 SRC96XLBP2S 2
UPS internal battery string + 1 SRC96XLBP2S +
1 SRC004 (1 additional battery string)
3
UPS internal battery string + 1 SRC96XLBP2S +
2 SRC004 (2 additional battery strings)
4
SRC96XLBP
The formula for configuring SRC96XLBP units is as follows:
UPS internal battery string + 3 x the number of SRC96XLBP units
# of battery
strings to be
entered
UPS internal battery string + 1 SRC96XLBP 4
UPS internal battery string + 2 SRC96XLBP units 7
UPS internal battery string + 3 SRC96XLBP units 10
Smart-UPS SRC UXI Models - Configure Number of Battery Strings
Each 96 V battery string consists of two 48 V battery modules. Count the number of battery strings being used and
enter that number.
Configuration # of Battery
Strings
Factory Default
for all Models
No UPS internal battery string 0
SRC96XLBP2S
1 SRC96XLBP2S 1
1 SRC96XLBP2S + 1 SRC004 (1 additional battery string) 2
1 SRC96XLBP2S + 2 SRC004 (2 additional battery strings) 3
SRC96XLBP
The formula for configuring SRC96XLBP units is as follows:
3 x the number of SRC96XLBP units
# of battery
strings to be
entered
1 SRC96XLBP 3
2 SRC96XLBP units 6
3 SRC96XLBP units 9