Datasheet
3Smart-UPS® VT, MGE™ Galaxy™ 3500 10-40 kVA 400 V Installation
Introduction
This manual is intended for certified electricians or APC-trained personnel installing the wall-mount
version of the Smart-UPS
®
VT, MGE™ Galaxy™ 3500 Maintenance Bypass Panel (MBP). It provides
detailed electrical installation instructions and physical specifications.
For additional information regarding the Smart-UPS VT, MGE Galaxy 3500 see the manuals
supplied with your UPS. You can find updates to this manual by clicking on the User
Manuals link on the Support page of the APC Web site (www.apc.com/support). In the list
of UPS manuals, look for the latest letter revision (A, B, etc.) of the part number on the back
cover of this manual.
Receiving the MBP
Initial inspection
Follow these steps upon receipt of the Maintenance Bypass Panel:
Inspect the box for any obvious signs of rough handling or external damage.
Transport the box to the installation site using a dolly or a hand truck.
At the installation site, open the box and remove the MBP enclosure.
Use the enclosed key to open the front door and inspect the unit for any signs of internal damage.
Note: The key is shipped in a plastic bag inside of the box
Note any damages that you observed during the external or internal inspection and immediately report the
damages to the shipping carrier. Allow their personnel to conduct an equipment inspection, if necessary.
Make your damage claim as specific as possible. If the carrier conducts an inspection, be sure to obtain a
copy of the inspection report for your records.
Contact APC using a phone number listed on the back cover of this manual. Inform the representative of
the condition of the shipment and of your damage claim with the carrier.
Note: Be sure to contact the shipping carrier before contacting APC.