Datasheet

13Smart-UPS® VT, MGE™ Galaxy™ 3500 10-40 kVA 400 V Installation
Specifications
Electrical 10-20 kVA 30-40 kVA
Input
Nominal voltage 380/400/415V 4W + GND 380/400/415V 4W + GND
Output
Nominal voltage 380/400/415V 4W + GND 380/400/415V 4W + GND
Wiring (only use copper conductors suitable for at least 75°C)
Maximum cable size 16mm² 35mm²
System output/ UPS output cable 10mm² 25mm²
System input/UPS input cable 10mm² 25mm²
Physical
Dimensions (H × W × D)
MBP 315 × 305 × 125mm
(12.4 × 12.0 × 4.9in)
460 × 400 × 125mm
(18.1 × 15.7 × 4.9in)
Shipping 442 × 305 × 175mm
(17.4 × 12.0 × 6.9in)
587 × 400 × 175mm
(23.1 × 15.8 × 6.9in)
Weight
MBP 7.0kg (15.4lb) 11.0kg (24.3lb)
Shipping 7.7kg (17.0lb) 12.3kg (27.0lb)
Environmental
Operating environment Indoor use only, protect from water and conductive contaminates
Temperature (operating and storage) 0° to 40°C (32° to 104°F)
Humidity (operating and storage) 0 to 95%, non-condensing
Pollution degree 2
Protection class IP 30
Compliance
Approvals CE