11Smart-UPS® VT, MGE™ Galaxy™ 3500 10-40 kVA 400 V Installation
UPS connections.
See your Smart-UPS VT, MGE Galaxy 3500 10–40 kVA Installation manual for instructions
on how to connect wiring at the UPS.
Caution: Connect all cables and wires according to the labels on the switches or on the
terminal block, as required.
Connect the four UPS inputs (N, L1, L2, L3) to the Q1 switch in the MBP. Use a Phillips or standard
screwdriver, and torque to 7Nm (60in-lbs).
Connect the four UPS outputs (N, L1, L2, L3) to the Q2 switch in the MBP. Use a Phillips or standard
screwdriver, and torque to 7Nm (60 in-lbs).
Connect the two UPS control wires to Pins 1 and 2 at the MBP control terminal block. Use a small
standard screwdriver, and hand-tighten the screws.