Datasheet

Smart-UPS® VT, MGE™ Galaxy™ 3500 10-40 kVA 400 V Installation10
External cable connections
Route the external cables to the MBP through the knockouts that you created in either the top or bottom
plate of the unit. If you did not create knockouts prior to mounting the MBP to the wall, do so at this
time. See “Create knockouts for cable access” on page 7 for instructions.
Note: The cables are colored per local code.
Utility connections.
Caution: Connect all cables and wires according to the labels on the switches and studs.
Connect the four inputs (N, L1, L2, L3) from the mains utility to the terminals on top of the Q1 switch.
Use a Phillips screwdriver and torque to 7Nm (60 in-lbs).
Connect the one PE input from the mains utility to one of the PE studs located above the Q3 switch using
an M6 washer, lock washer, and nut. Use an M8 wrench and torque to 27Nm (240 in-lbs).
N
L1
L2
L2 L3
NL1
L2 L3
NL1
L2 L3
Busbar