Datasheet

7Smart-UPS® VT, MGE™ Galaxy™ 3500 10-40 kVA 400 V Installation
Installation Procedure
Overview
Warning: Prior to beginning installation of the MBP, read and understand all safety
instructions provided in “Safety” on page 1.
• All internal cable connections and the Q3 to Q2 busbar connections are made at the factory prior
to shipment.
• All external cable connections with the UPS and mains must be made on-site. External cable is
not supplied with the shipment.
• All control wire connections between the UPS and the MBP must be made on-site. Control wires
are not supplied with the shipment.
Tools required
The installation procedures provided in this manual require the following tools and equipment:
Access the internal components
Access the internal components of the MBP by unlocking and opening the front door, using the key
provided with the shipment.
Create knockouts for cable access
Note: You can create knockouts for cable access either before or after you have mounted the
MBP to the wall. APC recommends creating all necessary knockouts prior to mounting the
MBP to the wall.
Using a knockout punch, create appropriate-sized holes for the grommet in either the top or bottom
plates of the MBP (depending on your wiring preference). For easier access when creating knockouts,
remove either plate by using a Phillips screwdriver to detach the eight screws that secure it to the
enclosure. The following illustration shows removal of the top plate.
Standard screwdriver Level
Phillips screwdriver Tape measure
M8 wrench Marker
Knockout punch Four (4) 6-mm hex-head lag bolts
Drill Four (4) flat washers