Datasheet

APC Service Bypass Panel
Bypass/UPS switch allows the
switching of the supply to the
load between the incoming
supply and the UPS, so the UPS
can be isolated for maintenance.
1
Equipment Outlets allowing
the SBP to support multiple
loads.
Output receptacle to feed
UPS input.
Equipment outlet circuit
breaker providing outlet
protection.
Utility input terminal block
access panel and hardwire
knockout.
Equipment output terminal
block access panel and
hardwire knockout.
2
3
4
5
6
7
Input receptacle to receive the
output from the UPS.
Standard features:
1
1
1
2
2
2
3
3
4
4
4
3
5
5
Input receptacle to receive the
external supply (utility).
SBP3000RMHW
SBP3000RMI
SBP1500RMI
6
7
8
8
Product feature SBP1500RMI SBP3000RMI SBP3000RMHW
NominalInput/Outputvoltage 230V 230V 230V
Maximumtotalcurrent 10A 16A 16A
Type/TransferTime
Externalsupply inputconnection IEC320C14 IEC320C20 Hardwire
UPSInput/Outputconnections IEC320C14/C13 IEC320C20/C19 IEC320C20/C19
Loadconnections IEC320C13(6) IEC320C13(6)+C19(1) Hardwire
Jumpercables (2)IE
C320C14toC13 (2)IEC320C20toC19 ( 1)IEC320C20toC19
Dime nsions(HxWxD)mm
Netweight(kg) 2.00 2.09 2.27
RegulatoryApprovals
StandardWarranty
EnvironmentalCompliance
2yearsrepairorreplace
CE
RoHS7bExemption,REACH:ContainsNoSVHCs
89.00x432.00x76.0
0
Input/Outputratings
Connecti ons
Physical
Conf ormance
Switchcharacteristics
BreakBeforeMake(BBM)/ 4msmax .