4.5.2 Hardware monitor
“Hardware monitor” can view the information of current voltages and temperatures.
Figure 4.5.2.1
If “Auto shutdown” is checked, the system will shutdown automatically when
voltage or temperature is out of the normal range. For better data protection, please
check “Auto Shutdown”.
For better protection and avoiding single short period of high temperature triggering
auto shutdown, the system use multiple condition judgments to trigger auto shutdown,
below are the details of when the Auto shutdown will be triggered.
1. There are several sensors placed on systems for temperature checking. System
will check each sensor for every 30 seconds. When one of these sensor is over
high temperature threshold for continuous 3 minutes, auto shutdown will be
triggered immediately.
2. The core processor temperature limit is 80 ℃ . The on board SAS device
temperature limit is 80℃. The backplane board temperature limit is 58℃.
3. If the high temperature situation doesn’t last for 3 minutes, system will not trigger
auto shutdown.