Specifications

2 Basic Rack Power Distribution Unit—Installation
Safety and Grounding
Please read the following information before
installing or operating your PDU:
This PDU is intended for indoor use
only.
Do not install this PDU where excessive
moisture or heat is present.
Never install any wiring, equipment, or
PDUs during a lightning storm.
Plug this PDU into a three-wire,
grounded power outlet only. The power
outlet must be connected to appropriate
branch circuit/mains protection (fuse or
circuit breaker). Connection to any other
type of power outlet may result in a
shock hazard.
Use only the supplied brackets for
mounting.
Do not use extension cords or adapters
with this PDU.
Do not work alone under hazardous
conditions.
Check that the power cord, plug, and
socket are in good condition.
To reduce the risk of electric shock when
grounding cannot be verified, disconnect
the PDU from the power outlet before
installing or connecting equipment.
Reconnect to the power outlet only after
making all connections.
Equipment must have a protective earth
connector which carries the leakage
current from the load devices (computer
equipment). Do not exceed a total
leakage current of 3.5 mA.