Specifications
DisplayMessageMeaningCorrectiveAction
StaticBypassSwitchModule
Removed
Thesystemnolongerdetectsastatic
bypassswitchmodule.
Option1:Ensurethatthestatic
bypassswitchmoduleisinstalled
properly.
Option2:CallSchneiderElectric
CustomerSupportforreplacement
ofthestaticbypassswitchmodule.
SysteminMaintenanceBypassThesystemisinmaintenance
bypass:theQ2breakerisopenand
theQ3breakerisclosed.
Nocorrectiveactionnecessary.
SystemPowerSupplyCardFaultThesystempowersupplycardhas
failedandrequiresreplacement.
Ensurethatthepowersupplycardis
installedproperly.See“Replacea
PowerManagementCard“.
SystemStart-UpCongurationFaultThesystemcongurationdownload
hasfailed.Unabletodeterminethe
systemvoltageorframesize.
Checkforotheralarmsandcontact
SchneiderElectricCustomer
Support(seethebackcover).
TechnicalcheckrecommendedRegularmaintenancerequirements
andtheendofservicelife
consumablecomponents.
ContactSchneiderElectricCustomer
Support(seethebackcover).
WarrantyexpiringsoonTheendofthecontractuallegal
warranty.
ContactSchneiderElectricCustomer
Support(seethebackcover).