Specifications

Storageofthebatterymodules:
Thebatterymodulesmustbestoredindoorsandwiththeirprotectivepackagingstillinplace.
Ambienttemperature:-15to40°C
(5to104°F)
Relativehumidity:25–85%
Non-condensing
Storeinaplacefreefrom:vibration,
dust,directsunlight,andmoisture
Storedbatteriesmustberechargedatregularintervalsdependingonthestoragetemperature:
StoragetemperatureRechargeinterval
-15to20°C(5to68°F)9months
20to30°C(68to86°F)6months
30to40°C(86to104°F)3months
Caution:Donotstorethebatteriesformorethan12months.
Caution:Twopersonsareneededforliftingcomponentsweighing18–32kg(40–70lb).
1.Holdingthehandle,gentlyliftthebatteryunitandpullithalfwayout.Alockingmechanism
preventsthebatteryunitfrombeingpulledallthewayout.
2.Releasethelockingmechanismbyliftingthebatteryunit.Pullthebatteryunitcompletelyout
whilesupportingit.
3.Takethereplacementbatteryunitandpushitintothesystem.
990–3015E-001
Symmetra™PX48,96,and160kW400V100kW208VOperation
29