Specifications

ReplaceaPowerModule
WARNING:Beforeremovinganypowermodules,makesurethattheremainingpower
modulescansupporttheload.
WARNING:Twopeopleareneededtoliftcomponentsweighingbetween18–32kg
(40–70lbs).
1.Turnthelockinglatchuntilthearrowpointsdownwards.
2.Unscrewthespring-activatedknobsonbothsidesofthemodule.
3.Pullthemoduleupandoutoftheenclosureasfarasthelockmechanismwillallow.
4.Releasethelockbypressingtheblackplastictabonbothsidesofthemodule.
5.Pullthemoduleoutoftheenclosure.
6.Pushthereplacementmodulesecurelyintotheenclosure.
Caution:Donotattempttoinsertthepowermoduleusingexcessiveforce,butmakesure
thatitisinplacebeforecontinuing.
7.Tightenthespring-activatedknobsonbothsidesofthemoduletoensurepropercontact.
8.Securethelockinglatchtostartthepowermodule.
Caution:Tightenthespring-activatedknobsbeforesecuringthelockinglatchtoensure
thatthemodulemakespropercontactwithintheunit.Thepowermodulewillnotoperate
unlessthelockinglatchisengaged.Ifithasnotengaged,takeoutthepowermoduleand
insertitagain.
990–3015E-001
Symmetra™PX48,96,and160kW400V100kW208VOperation
27