Specifications
ChangetheDateandTime
1.SelectAdminandpressENTER.
UPSAlarms
PowerDistLog
SwitchGear→Admin
EnvironmentHelp
2.SelectDate/TimeandpressENTER.
NetworkSetup
LocalInterface
→Date/Time
DeviceID
3.SelectDateorTimeandchangethesettings
byusingtheUPandDOWNarrowkeys.Press
ENTERtosavethechanges.
Mode:Manual
Format:mm/dd/yyyy
Date:xx/xx/xxxx
Time:xx:xx:xx
CongureInputContacts
1.SelectEnvironmentandpressENTER.
UPSAlarms
PowerDistLog
SwitchGearAdmin
→EnvironmentHelp
2.SelectInputContactsandpressENTER.
→InputContacts
OutputRelays
AlarmRelayMap
3.Selectdesiredoutputrelay,1through4,select
Conguration,andpressENTER.
InputContact:xof4
<contactname>
Status:Normal
→Configuration
4.Changethesettingsforname/location,alarms,
severity,andnormalstate.
Name/Locationx
Alarms:Enabled
Severity:Critical
Normal:Open
22
Symmetra™PX48,96,and160kW400V100kW208VOperation
990–3015E-001