Specifications
8.SelectTurnUPSOnintoBypassandpress
ENTER.
TurnUPSOn
→UPSOnintoBypass
9.SelectContinueTurnOnandpressENTER.
Batteryback-upnot
availableinbypass!
>Cancel
→>ContinueTurnOn
10.ConrmbyselectingY es,OnIntoBypass
andpressENTER.
Confirm:
UPSonIntoBypass
>NO,ABORT
→>Yes,OnIntoBypass
11.WaitfortheUPStoturntheloadon.
TurningUPSonInto
Bypass.
Pleasewait...
12.TheUPSisnowON.
Note:TheH2LEDnexttotheQ2
switchwillturnon,indicatingthatit
issafetooperatetheQ2switch.
UPS’soutputisnow
inbypass
Pressanykey...
13.SettheQ2switchonthePDU,PDU-XRor
theexternalmaintenancebypasspaneltothe
ONposition.
Note:TheH3LEDnexttotheQ3
switchwillturnon,indicatingthatit
issafetooperatetheQ3switch.
14.SettheQ3switchtotheOFFposition.
15.UsethedisplayinterfacetotransfertheUPS
outofbypass:
16.SelectUPSandpressENTER.
→UPSAlarms
PowerDistLog
SwitchGearAdmin
EnvironmentHelp
17.SelectUPSPowerControlandpressENTER.
→UPSPowerControl
UPSStatus
UPSTests&Diags
UPSConfiguration