Specifications
PDUXR(ifapplicable)andonthemainframe
(onlyPX48).
ReturntoNormalOperationfromMaintenanceBypassOperation
1.SettheDCDISCONNECTswitchtotheON
positiononallXRBatteryEnclosuresandthe
PDU-XR(ifapplicable)andonthemainframe
(onlyPX48).
2.SettheQ1switchtotheONposition.
3.SettheSYSTEMENABLEswitchontheUPS
totheONposition.
Note:Waitapproximatelytwo
minutesforthesystemtostart.
4
4.SettheQ5breakertotheONposition(if
applicable).
5.UsethedisplayinterfacetoturntheUPSload
on.
6.SelectUPSandpressENTER.
→UPSAlarms
PowerDistLog
SwitchGearAdmin
EnvironmentHelp
7.SelectUPSPowerControlandpressENTER.
→UPSPowerControl
UPSStatus
UPSTests&Diags
UPSConfiguration
16
Symmetra™PX48,96,and160kW400V100kW208VOperation
990–3015E-001