Specifications
7.SettheUPSSYSTEMENABLEswitchtothe
OFFposition.
8.SettheQ2switchtotheOFFposition.
9.SettheQ1switchtotheOFFposition.
10.SettheQ5breakertotheOFFposition(if
applicable).
11.Verifythatthemaintenancebypassswitch
(Q3)isintheOFFposition.
7
12.SettheDCDISCONNECTswitchonallof
theXRBatteryEnclosuresandthePDU-XR
(ifapplicable)andonthemainframe(onlyfor
PX48)totheOFFposition.
XRBatteryEnclosures/PDU-XR
13.Disconnectallbatteryunitsbyremovingthem
orpullingthemouttothereddisconnectline.
Caution:Toensurethatthe
enclosuredoesnottip,donotpull
outthebatteryunitsbeyondthered
disconnectline.Ifyouintendto
completelyremovethebatteryunits,
removethemfromtheenclosureone
atatime.Failuretopullbatteryunits
outtothereddisconnectlinecould
causedeepdischarge/damagetothe
batteries.
14.SettheupstreammainspowertotheOFFor
LOCKEDOUTposition.IftheUPShasadual
mainssupply,setbothsuppliestotheOFFor
LOCKEDOUTposition.
15.Measurebypass/outputDCandmainsto
ensurethatthesystemiscompletelypowered
off.
990–3015E-001
Symmetra™PX48,96,and160kW400V100kW208VOperation
9