Specifications

PerformaTotalPowerOff
WARNING:Thisprocedurewilldisconnecttheload.
Note:Ifshutdownviathedisplayisdisabled,thenyoucannotperformthisprocedureand
themessage:Commandnotallowed,UPSconguredtonevershutdownappears.If
youwanttoenableshutdownviathedisplay,thisisdonebyaFieldServiceEngineervia
theUPSTuner.
1.SelectUPSandpressENTER.
UPSAlarm
PowerDistLog
SwitchGearAdmin
EnvironmentHelp
2.SelectUPSPowerControlandpressENTER.
UPSPowerControl
UPSStatus
UPSTests&Diags
UPSConfiguration
3.SelectTurnUPSOffandpressENTER.
TurnUPSOff
RebootUPS
UPSintoBypass
UPStoSleep
4.SelectNo,Don’tNotifytoshutdownwithout
delayandpressENTER.
Note:Thisactionwillcutallpower
totheloadwithoutshuttingitdown
rst.Ifyouwanttoshutdownthe
serversrst,thenchooseYes,Notify
Servers.Notethatthisfunction
isonlyavailableforserverswith
PowerChute.
NotifyPowerChute?
Cancel
Yes,NotifyServers
No,Don'tNotify
5.ConrmYES,TurnUPSOffandpress
ENTER.
TurnUPSoff
WithoutServer
Notification?
>NO,ABORT
→>YES,TurnUPSOff
6.WaitfortheUPStoturnoff.
TurningUPSoff,
pleasewait...
8
Symmetra™PX48,96,and160kW400V100kW208VOperation