Operation Symmetra™ PX 48, 96, and 160 kW 400 V 100 kW 208 V
Legal Disclaimer The information presented in this manual is not warranted by the Schneider Electric IT Corporation to be authoritative, error free, or complete. This publication is not meant to be a substitute for a detailed operational and site specific development plan. Therefore, Schneider Electric IT Corporation assumes no liability for damages, violations of codes, improper installation, system failures, or any other problems that could arise based on the use of this Publication.
Table of Contents About this Manual .......................................................................................................... 1 Companion Manuals ................................................................................................... 1 Find Updates to this Manual ..................................................................................... 1 Overview .........................................................................................................................
Troubleshooting ..............................................................................................................32 Status and Alarm Messages .....................................................................................32 Display Messages ......................................................................................................32 Modular Distribution Fault List ................................................................................36 PDU Fault List .................
About this Manual This manual is for: • Symmetra PX 48 kW 400 V UPS • Symmetra PX 96 and 160 kW 400 V UPS and Power Distribution Unit (PDU-XR) • Symmetra PX 100 kW 208 V UPS and Power Distribution Unit (PDU) • XR Battery Enclosure Companion Manuals For additional information, see the following Symmetra PX manuals: • Receiving and Unpacking (990-3013) • Safety (990-2984) • 96 and 160 kW 400 V Installation (990-3017) • 48 kW 400 V Installation (990-3151) • 100 kW 208 V Installation (990-3659) • 48 kW 400 V X
Overview User Interface A LOAD POWERED LED When this LED is green, power to the load is on. When the LED is yellow, the load is supplied through the batteries. When the LED is flashing yellow, the unit is in bypass. B CHECK LOG LED When this LED is green, a new event has been added to the event log. C WARNING LED When this LED is yellow, there are one or more warning alarms in the system. D CRITICAL LED When this LED is red, there are one or more critical alarms in the system.
Display Interface Overview Screens The Overview Screen is the main entrance to the user functions of the display interface. The UP/DOWN navigation keys take you from one screen to another. When the system is running, the display will scroll through screens showing information about the system and any active alarms. Note: The data values shown are for example only.
Main Menu Screen From the main menu it is possible to configure and monitor the system through the sub menu screens: UPS, Power Dist, Switchgear, Environment, Alarms, Log, Admin, and Help. Use the UP and DOWN arrow keys to navigate through the menu screens.
Menu Tree The menu tree provides a quick overview of the functions and views you may access.
Caution: The display provides access to more functions than described in this manual. Those functions should not be accessed without the assistance of Schneider Electric Customer Support in order to avoid unwanted load impacts. For Schneider Electric World-Wide Customer Support, refer to the back cover of this manual. If you by accident go beyond the functions described, press ESC to return to previous screens.
Operation Modes In an installation that does not include a maintenance bypass panel, the UPS has three operation modes: normal operation, battery operation and static bypass operation. If the installation includes a PDU, a PDU-XR, or an external maintenance bypass panel, the mode maintenance bypass operation also becomes available. Normal Operation During normal operation, the UPS converts the utility/mains supply to conditioned power for the connected load.
Perform a Total Power Off WARNING: This procedure will disconnect the load. Note: If shutdown via the display is disabled, then you cannot perform this procedure and the message: Command not allowed, UPS configured to never shutdown appears. If you want to enable shutdown via the display, this is done by a Field Service Engineer via the UPSTuner. 1. Select UPS and press ENTER. → UPS Alarm Power Dist Log Switch Gear Admin Environment Help 2. Select UPS Power Control and press ENTER.
7. Set the UPS SYSTEM ENABLE switch to the OFF position. 7 8. Set the Q2 switch to the OFF position. 9. Set the Q1 switch to the OFF position. 10. Set the Q5 breaker to the OFF position (if applicable). 11. Verify that the maintenance bypass switch (Q3) is in the OFF position. 12. Set the DC DISCONNECT switch on all of XR Battery Enclosures/PDU-XR the XR Battery Enclosures and the PDU-XR (if applicable) and on the main frame (only for PX48) to the OFF position. 13.
Start the System after Total Power Off 1. Set the upstream utility/mains power to the XR Battery Enclosures/PDU-XR ON or LOCKED IN position. If the UPS has a dual mains supply, set both supplies to the ON or LOCKED IN position. 2. Set the DC DISCONNECT switch to the ON position on all XR Battery Enclosures and the PDU-XR (if applicable) and on the main frame (only PX 48). 3. Set the Q1 switch to the ON position. 4. Set the SYSTEM ENABLE switch on the UPS to the ON position.
10. Confirm by selecting Yes, Turn UPS On and press ENTER. Confirm: Turn UPS On ? >NO, ABORT → >Yes, Turn UPS On 11. Wait for the UPS to turn on. Turning UPS on, Please wait...
Turn the UPS Load Off 1. Select UPS and press ENTER. → UPS Power Dist Switch Gear Environment Alarms Log Admin Help 2. Select UPS Power Control and press ENTER. → UPS Power Control UPS Status UPS Tests & Diags UPS Configuration 3. Select Turn UPS Off and press ENTER. → Turn UPS Off Reboot UPS UPS Into Bypass UPS To Sleep 4. Select No, Don’t Notify and press ENTER. Note: This action will cut all power to the load without shutting it off first.
Turn the UPS Load On 1. Select UPS and press ENTER. → UPS Power Dist Switch Gear Environment Alarms Log Admin Help Press 2. Select UPS Power Control and press ENTER. → UPS Power Control UPS Status UPS Tests & Diags UPS Configuration Press 3. Select Turn UPS On and press ENTER. → Turn UPS On UPS On Into Bypass Press 4. Confirm by selecting Yes, Turn UPS On and press ENTER. Confirm: Turn UPS On? >NO, ABORT → >YES, Turn UPS On Press 5. Wait for the UPS to turn the load on.
Transfer the UPS into Maintenance Bypass Operation Note: If shutdown via the display is disabled, then you cannot perform this procedure and the message: Command not allowed, UPS configured to never shutdown appears. If you want to enable shutdown via the display, this is done by an Field Service Engineer via the UPSTuner. 1. Select UPS and press ENTER. → UPS Power Dist Switch Gear Environment Alarms Log Admin Help 2. Select UPS Power Control and press ENTER.
9. Select UPS and press ENTER. → UPS Power Dist Switch Gear Environment Alarms Log Admin Help 10. Select UPS Power Control and press ENTER. → UPS Power Control UPS Status UPS Tests & Diags UPS Configuration 11. Select Turn UPS Off and press ENTER. → Turn UPS Off Reboot UPS UPS into Bypass UPS to Sleep 12. Select No, Don’t Notify and press ENTER. Notify PowerChute ? Cancel Yes, Notify Servers → No, Don't Notify 13. Confirm by selecting YES, Turn UPS Off and press ENTER.
PDU XR (if applicable) and on the main frame (only PX 48). Return to Normal Operation from Maintenance Bypass Operation 1. Set the DC DISCONNECT switch to the ON position on all XR Battery Enclosures and the PDU-XR (if applicable) and on the main frame (only PX 48). 2. Set the Q1 switch to the ON position. 3. Set the SYSTEM ENABLE switch on the UPS to the ON position. 4 Note: Wait approximately two minutes for the system to start. 4. Set the Q5 breaker to the ON position (if applicable). 5.
8. Select Turn UPS On into Bypass and press ENTER. Turn UPS On → UPS On into Bypass 9. Select Continue Turn On and press ENTER. Battery back-up not available in bypass! >Cancel → >Continue Turn On 10. Confirm by selecting Yes, On Into Bypass and press ENTER. Confirm: UPS on Into Bypass >NO, ABORT → >Yes, On Into Bypass 11. Wait for the UPS to turn the load on. Turning UPS on Into Bypass. Please wait... 12. The UPS is now ON.
18. Select UPS out of Bypass and press ENTER. Turn UPS Off Reboot UPS → UPS out of Bypass UPS to Sleep 19. Confirm by selecting Yes, Out of Bypass and press ENTER. Confirm: UPS out of Bypass? >NO, ABORT → >YES, Out of Bypass 20. Wait for the UPS to transfer out of bypass. Putting UPS out of Bypass, please wait.... 21. The UPS is now out of bypass and is in normal operation. 18 UPS is now out of bypass Press any key....
View the Status Screens 1. Select UPS and press ENTER. → UPS Power Dist Switch Gear Environment Alarms Log Admin Help 2. Select UPS Status and press ENTER. UPS Power Control → UPS Status UPS Tests & Diags UPS Configuration 3. Use the UP and DOWN arrow keys to navigate through the Status screens. Symmetra PX 160 kW Status: On Line No UPS Alarms View the Log Screen 1. Select Log and press ENTER. UPS Power Dist Switch Gear Environment Alarms →Log Admin Help 2.
Configuration System Settings Set Up the Network 1. Select Admin and press ENTER. UPS Power Dist Switch Gear Environment Alarms Log → Admin Help 2. Select Network Setup and press ENTER. → Network Setup Local Interface Date/Time Device ID 3. Select Mode and press ENTER. Stat: → Mode: IP: SM: 4. Select Fixed IP Addr to give a specific IP address to the UPS system or select one of the other three methods to obtain an IP address. In this example Fixed IP Addr mode is selected.
Change the Display Interface Settings 1. Select Admin and press ENTER. UPS Power Dist Switch Gear Environment Alarms Log → Admin Help 2. Select Local Interface and press ENTER. Network Setup → Local Interface Date/Time Device ID 3. Select Display Behavior and press ENTER. Local Password → Display Behaviour Alarm Beeper 4. Select Contrast, Key Click, Beeper Volume, or Check Log Light and change the settings using the UP and DOWN arrow keys. Press ENTER to save the changes.
Change the Date and Time 1. Select Admin and press ENTER. UPS Power Dist Switch Gear Environment Alarms Log → Admin Help 2. Select Date/Time and press ENTER. Network Setup Local Interface → Date/Time Device ID 3. Select Date or Time and change the settings by using the UP and DOWN arrow keys. Press ENTER to save the changes. Mode: Manual Format: mm/dd/yyyy Date: xx/xx/xxxx Time: xx:xx:xx Configure Input Contacts 1. Select Environment and press ENTER.
Configure Output Relays 1. Select Environment and press ENTER. UPS Power Dist Switch Gear → Environment Alarms Log Admin Help 2. Select Output Relays and press ENTER. Input Contacts → Output Relays Alarm Relay Map 3. Select desired output relay, 1 through 4, select Configuration, and press ENTER. Input Contact:xof4 Status: Closed → Configuration 4. Change the settings for name and normal position for the selected output relay.
Maintenance Life Cycle Monitoring (LCM) The Life Cycle Monitoring (LCM) function provides UPS maintenance advice to guarantee installation availability for the user. The display gives three messages enabling the following to be identified.
To return a failed module to Schneider Electric, pack the module in the original shipping materials, and return it by insured, prepaid carrier. The Schneider Electric Customer Support representative will provide the destination address. If you no longer have the original shipping materials, ask the representative about obtaining a new set. Pack the module properly to avoid damage in transit.
Replacement Parts WARNING: All safety instructions in the Safety sheet (990-2984) should be read, understood, and followed prior to handling the system. Failure to do so could result in equipment damage, serious injury, or death. WARNING: Only trained persons familiar with the construction and operation of the equipment, as well as the electrical and mechanical hazards involved, may install and remove system components. Note: A maximum of two SmartSlots can be used.
Replace a Power Module WARNING: Before removing any power modules, make sure that the remaining power modules can support the load. WARNING: Two people are needed to lift components weighing between 18–32 kg (40–70 lbs). 1. Turn the locking latch until the arrow points downwards. 2. Unscrew the spring-activated knobs on both sides of the module. 3. Pull the module up and out of the enclosure as far as the lock mechanism will allow. 4.
Replace a Battery WARNING: Servicing of batteries should be performed or supervised by personnel knowledgeable about batteries and the required precautions. Caution: When replacing batteries, replace with same type and number of batteries or battery packs. Caution: Risk of explosion if battery is replaced by an incorrect type. Dispose of the batteries according to the instructions. Caution: Do not dispose of batteries in a fire. The batteries may explode. Caution: Do not open or mutilate batteries.
Storage of the battery modules: The battery modules must be stored indoors and with their protective packaging still in place.
Note: When replacing batteries, always replace both batteries A+B or C+D (see illustration above) as they are interconnected in pairs. For four batteries in a row it is recommended to replace all four at the same time to ensure optimal run-time (Example 1). The batteries can also be replaced in twos, but always A+B (Example 2) or C+D (Example 3). For two batteries in a row, always replace both batteries at the same time (Example 4).
Replace a Power Distribution Module Note: The load that is connected to the actual power distribution module will not be supported when the locking latch on the module is opened. 1. Switch the breakers to the OFF position. 2. Disconnect the power cable from the power distribution module’s extension cable or Rack-Mount PDU. 3. Open the locking latch on the module and gently pull the module out of the enclosure. 4. Take the replacement power distribution module and open the locking latch.
Troubleshooting WARNING: Only trained persons familiar with the construction and operation of the equipment, as well as the electrical and mechanical hazards involved, may install and remove system components. Status and Alarm Messages This section lists the status and alarm messages that the UPS might display. The messages are listed in alphabetical order, and a suggested corrective action is listed with each alarm message to help you troubleshoot problems.
Display Message Meaning Corrective Action Extended Run Frame Fault One of the battery enclosures has failed. Contact Schneider Electric Customer Support (see the back cover). External DC Disconnect Switch Open The external DC DISCONNECT switch tripped. Battery power is not available or the runtime is lower than expected. Close the external DC DISCONNECT switch. If the problem continues, call Schneider ElectricCustomer Support.
Display Message Meaning Corrective Action No Power Modules Detected No power modules are available. Option 1: Ensure that the power modules are properly installed, the two fastening screws are tight, and the locking latch is engaged. Option 2: Check for other communication alarm messages in the log. Not Synchronized Fault System cannot synchronize to AC line and bypass mode may not be available. Option 1: Decrease the sensitivity to input frequency.
Display Message Meaning Corrective Action Static Bypass Switch Module Removed The system no longer detects a static bypass switch module. Option 1: Ensure that the static bypass switch module is installed properly. Option 2: Call Schneider Electric Customer Support for replacement of the static bypass switch module. System in Maintenance Bypass The system is in maintenance bypass: the Q2 breaker is open and the Q3 breaker is closed. No corrective action necessary.
Modular Distribution Fault List The display interface will identify the number of the power distribution modules that has caused an alarm or warning. Display Message Meaning Corrective Action High Module Current Alarm The threshold of the high module current has been exceeded. Evaluate the threshold setting. If necessary, adjust it for your situation. High Subfeed Current Alarm The threshold of the high subfeed current has been exceeded. Evaluate the threshold setting.
PDU Fault List Display Message Meaning Corrective Action System In Maintenance Bypass The system is in maintenance bypass: the Q2 switch is open and the Q3 switch is closed. No corrective action necessary. Min Output Voltage Alarm Phase-to-neutral output voltage for phase has dropped below the configured limit. Evaluate the threshold setting. If necessary, adjust it for your situation. Max Output Voltage Alarm Phase-to-neutral output voltage for phase exceeded the configured limit.
Worldwide Customer Support Customer support is available at no charge via e-mail or telephone. Contact information is available at www.apc.com/support/contact © Schneider Electric. APC and the APC logo are owned by Schneider Electric Industries S.A.S. or their affiliated companies. All other trademarks are property of their respective owners.