User Manual

APC warrants its Panelmount SPD products against defects in workmanship and materials for 5
years from the date of original purchase. The panelmount SPD must be installed by a qualified
and licensed electrician in order to qualify for warranty protection.
Liability is limited to the replacement of the defective product. A Return Material Authorization
(RMA) must be given by APC prior to the return of any product (see Technical Support and
Customer Service). A copy of the invoice from the installer (electrician or electrical service
company) must accompany the defective device being returned. If the return of a device is
authorized by APC, APC will immediately ship a replacement unit to the customer. Along with
the replacement unit, APC will include a pre-paid shipping tag for the return of the originally
defective unit. The replacement unit will not be warranted unless the defective unit is received
by APC.
Under no circumstance is APC responsible for the cost of removal or installation of any panel-
mount SPD.
The company specifically disclaims all other warranties, expressed or implied. Additionally, the
company will not be responsible for incidental or consequential damages resulting from any
defect in any product or component thereof.
Technical Support and Customer Service
United States and Canada: 1-800-800-4APC
This manual, as well as information about the entire APC product line are available on the inter-
net at: www.apc.com. Prior to calling APC for technical assistance or ordering parts, please
have the following information available:
Model Number of unit: _______________________________________________
Serial Number of unit: _______________________________________________
Manufacture Date: _______________________________________________
Purchase Date: _______________________________________________
Your Order Number: _______________________________________________
Return Shipment Address: American Power Conversion Corporation
1600 Division Road
Dock 25
West Warwick, Rhode Island 02893 USA
Attn: RMA#
The panelmount SPD can be flush-mounted when the application requires a more aes-
thetic installation. To install the SPD using the FMK2, proceed as follows:
1. Ensure power to the panelboard has been removed.
2. Remove the screws securing the outer panelboard cover to the distribution panel-
board (panelboard) (see Figure 1).
3. Select the location where the SPD and Flush Mount Kit (FMK2) will be
mounted. The location should be based on the internal configuration of the panel-
board and the physical surroundings outside the panelboard). Note that the SPD’s
lead length must be minimized to achieve maximum performance. Aesthetics
may have to be sacrificed in order to achieve maximum surge protection.
4. Place the Flush Mount Kit panel where it will be mounted and trace the center
hole and mounting holes. Cut this shape into the mounting surface and mount the
FMK2 panel to the mounting surface.
5. Install the panelmount SPD to the backside of the Flush Mount Kit panel using
the four 8-32 x 5/8" Thread Cutting Screws (provided with the FMK2).
6. Drill or punch a 7/8" hole in the top, side or bottom surface of the panelboard in
accordance with the location of the FMK2.
7. Push the leads from the panelmount SPD through the 7/8" diameter hole toward
the inside of the panelboard.
8. Trim the leads from the SPD as short as possible, but still allowing the following
connections to be made (Note: Black wires go to the first 20 amp circuit breaker):
Black wires (two or three in number) go to the nearest free circuit breaker. In
all installations, it is not critical which black wire goes to the positions on the
circuit breaker. The phase of each lead is marked with a white band and letter
designator (A, B, or C). Connect the SPD leads to the appropriate phase.
Connect the white Neutral wire to the neutral bar using a set screw (in some
applications, this connection may not be required).
Connect the green Ground wire to the panelboard ground.
9. Install the panelboard cover. Note: Conducting dielectric and/or high potential
testing will cause internal damage to the SPD unit. Do not perform dielectric or
high potential tests with the phase or neutral SPD wires connected.
10. Install any included warning labels near the panelmount SPD. Ensure the labels
are placed where they will be visible at all times.
11. Apply power to the panelboard. Depending on the PM 2 model, either 2 (split-
phase applications) or 3 (3 phase applications) LEDs will illuminate on the SPD.
If any connected phase LED on the SPD does not light, remove power, check all
connections and test again. If any connected phase LED still does not illuminate,
contact APC Customer Service at 1-800-800-4APC or APC Technical Support at
www.apc.com on the internet.
Item Specification
Voltage Rating PMP2X = 120/240V Split Phase.
PMF2X = 120/208V Three Phase, WYE.
PMG2X = 277/480V Three Phase, WYE.
Temperature - Operating
Temperature - Storage
-40
o
C (-40
o
F) to +60
o
C (+140
o
F).
-55
o
C (-67
o
F) to +60
o
C (+140
o
F).
Audible Noise None
Service Clearance 36 inches (94.1 cm) in front of the unit.
Installation Type Chase Nipple
Wire Length vs. Response Time and Let-
Through Voltage
1 foot (31.7 cm) of wire = 1 nanosecond.
175 volts per foot (6kV/3kA, 8/20 microsec-
onds) are added to the clamp voltage.
Wire Size and Installation Torque Wire Size = #12 AWG, Torque to 18 in. lbs.
Circuit Breaker Connection 20 amp
System Grounding Per IEEE STD 142-1991. For sensitive elec-
tronics/computer systems, the recommended
ground impedance is 25 ohms or less.
Warranty and Service
Specifications
990-0523 10/00 Copyright © 2000 American Power Conversion. All rights reserved.
5
How to Install the SPD and Flush Mount Kit (p/n: FMK2)
Mounting
Surface
SurgeArrest
PM 2 Series
Mounting Screws
Phase, Ground
and Neutral Wires
Figure 4. PM 2 Series SPD Flush-Mount Kit Installation
SPD
Flush-Mount
Kit Screws
(8-32 x 5/8" Thread Cutting)
4 places, through plate
into SPD)
Removed
Material
Flush-Mount
Plate
(side view, typical)
Figure 3. Typical Parallel Connections
Phase A (black)
Neutral (white)
Ground (green)
Neutral Bus
Ground Bus
Phase C
Neutral
(if used)
Ground
To "Protected" Loads
Mounting
Surface
SurgeArrest
PM 2 Series SPD
Mounting Screws
flange into mounting
Figure 2. PM 2 Series SPD Installation
(side view, typical)
Phase, Ground
and Neutral Wires
Phase B (black)
Phase C (black)
Surge Protection
Device (SPD)
Phase B
Phase A
Wiring through Chase
* Minimize Length
* Avoid Sharp Bends
Nipple and Conduit to the
Breaker Panel
Breaker Panel
(4 places, through
mounting plate into
mounting surface -
not provided)
surface - not provided)
(4 places, through