Grounding
The SPD has leakage current to ground when energized and can present a
hazardous touch voltage.
Figure 2: Surge Protective Device Wiring Practice
To load(s)
Phases
Neutral
Ground
Ground bus
Neutral bus
SPD
Phase A
Phase B
Phase C
Neutral
Ground
Panel
Interconnect wiring
– Minimize length
– Avoid sharp bends
WARNING
HAZARDOUS TOUCH VOLTAGE
Connect the SPD ground terminal to the building grounding grid
structure.
Use an appropriately sized equipment grounding conductor.
When using metallic raceway or conduit:
Do not use the SPD ground unless augmented with an insulated
equipment grounding conductor installed inside the metallic raceway or
conduit.
Do not use isolated bushings to interrupt the metallic raceway or
conduit.
Maintain electrical continuity at all raceway and conduit connections
using appropriate bonding devices.
Do not use a separate isolated ground for the SPD.
Verify proper equipment connection to the grounding system.
Verify ground grid continuity by performing regularly scheduled
inspections and testing as part of a comprehensive electrical
maintenance program.
Failure to follow these instructions can result in death or serious injury.