Specifications

ConnectCommunicationWiresinInstallationswith
PDU
PDU
UPS
XR Battery
Enclosure
XR Battery
Enclosure
XR Battery
Enclosure
0P3199
0P4123
1
2
3
4
5
6
6
5
6
6
2
1
3
Front
J7
J8
J9
J1
1.RoutethebatterybreakertripcablefromJ1inthefirstXRBatteryEnclosuretotheJ3portinthe
nextXRBatteryEnclosure.RepeattheprocedureforallXRBatteryEnclosures.
2.RoutethebatterybreakertripcablefromJ1inthelastXRBatteryEnclosuretoJ27onthe
EPO/ancillaryinterfaceboard(0P4123)intheUPS(forremoteXRBatteryEnclosurethelength
ofthesignalmustnotexceed200m).
3.RoutethecommunicationcablefromXRCommunicationsport1ineachXRBatteryEnclosureto
port2inthenextXRBatteryEnclosure.Removetheterminatorwhennecessary.
4.RoutethecommunicationcablefromtheXRCommunicationsport1toport2inthelastXR
BatteryEnclosureintherowtotheUPSXRCommunicationsport2(forremoteXRBattery
Enclosurethelenghtofthesignalmustnotexceed200m).
5.IninstallationswithPDU,removejumperwireharnessbetweenJ1andJ2.
6.RoutethefourPDUcommunicationcablesfromthePDUtoJ7,J8,J9,andJ1onthemaintenance
bypassinterfaceboard(0P3199)intheUPS.
44
SymmetraPX100kW208V
990–3659C-001