Specifications
MaintenanceBypassPanelInterface
WARNING:Ensurethatthewiresareproperlyretainedandkeptawayfrom
high-voltagelinesandbreakers.
Make contact closure connections (N/O or N/C) to
monitor dry contacts. Up to eight connections can
be made - four input contacts and four output relays.
Output relays:
240 V / 8 A
0.3 VA / 1.9 kW
1/2 Q001 UPS input switch (N/O position)
3/4 Q002 UPS output switch (N/O position)
5/6 Q003 UPS service bypass switch
(N/C position)
7/8 OK to operate UPS output switch Q002
9/10 OK to operate service bypass switch
Q003
11/12 Not used
13/14 External switchgear present
Input signals: Contact load: TTL
990–3659C-001
SymmetraPX100kW208V
43